HP PowerTrust A3589A Manual page 137

5.5 kva rack-mounted ups
Table of Contents

Advertisement

• The UPS output has been turned off with the Output On/Output Off
switch. For this cause, use Action 1 below to recover.
• The UPS output has been turned off by a command from the host
computer system and has not been commanded to turn back on. For this
cause, use Actions 2 and 3 below to recover.
Abnormal causes of this case are:
• Faulty UPS Output On/Output Off switch and related internal UPS
components. For this cause, use Actions 2 and 3 below to recover.
Action:
1. Verify that the Output On/Output Off switch is in the
If it is, set it to
operation if all other conditions, such as, AC input voltage, load, and
UPS temperature, are normal.
2. If the Output On/Output Off switch is in the
following steps should be performed to recover the UPS output:
a. Set the UPS/Battery switch to
b. Set the Output On/Output Off switch to
3. If none of the steps above causes the UPS output to recover, the UPS is
defective.
Case 13 (Normal or Abnormal) — Deeply Discharged Batteries
or Non-Fatal UPS Failure
Indicators:
AC Output
Battery Power
Attention
Caution LED not lit
Enable lit
Audible Alarm: 1 beep every 10 seconds
Chapter 6
. This should cause the UPS to return to normal
Output On
back to
.
ENABLE
then set it back to
Output On
If the UPS returns to normal operation, that is, with the UPS
running on AC power, then it is either OK and must have entered
Automatic Bypass because the Bypass Switch Activation button was
pressed, or the UPS has an intermittent fault that occasionally puts
it in Automatic Bypass and then clears itself.
If the UPS stays in this condition—with the Service Bypass switch
in the
position and after toggling the Output On/Output Off
NORMAL
switch—it is defective.
lit
not lit
lit
UPS Halted (Has No AC Output)
Output On
for one second, and then set it
DISABLE
Output Off
.
Troubleshooting
position.
Output Off
position, the
for one second, and
6-21