HP PowerTrust A3589A Manual page 141

5.5 kva rack-mounted ups
Table of Contents

Advertisement

Attention
Caution LED not lit
Enable not lit
Audible Alarm: continuous
Meaning:
This case indicates that the UPS internal circuits have become dormant
after 30 minutes of operation in Automatic or Service Bypass mode (see
"Case 4 (Normal or Abnormal) — Bypass Mode"). The UPS enters this
state to minimize the rate of discharge of its batteries, since its battery
charging circuits are not functional while in Bypass mode.
Cause:
Normal causes of this case are:
• The UPS has been placed in Service Bypass for more than 30 minutes.
• The red Bypass Switch Activation Button of the UPS was depressed
(manually forcing the UPS in Automatic Bypass mode) at least 30
minutes earlier.
Abnormal causes of this case are:
• The UPS microprocessor detected a UPS internal failure and placed the
unit in Automatic Bypass mode. 30 minutes later, the UPS entered this
case.
• The Battery Box cable is not connected to the UPS Electronics Unit.
• The Battery Precharge Shorting Plate is not properly installed onto the
corresponding connector blades of the Electronics Unit.
• The UPS batteries are deeply discharged or dead.
Action:
1. Verify whether the Service Bypass switch is in the
use the procedure in "Placing the UPS in Service Bypass Mode" in
Chapter 4 to recover the UPS from Service Bypass mode.
2. If the Service Bypass switch is in the
Automatic Bypass Sleep mode. To determine if the UPS is in this
condition because of an internal UPS fault or because the red Bypass
Switch Activation Button was pressed, follow this procedure:
a. Place the UPS in Service Bypass mode using the procedure outlined
b. Set the UPS/Battery switch to
c. Set the Output On/Output Off switch to
Chapter 6
lit
"Placing the UPS in Service Bypass Mode" in Chapter 4. This action
prevents dropping the UPS output voltage during the rest of this
procedure.
back to
.
ENABLE
then set it back to
Output On
UPS Halted (Has No AC Output)
position, the UPS is in
NORMAL
for one second, and then set it
DISABLE
Output Off
.
Troubleshooting
position. If so,
Bypass
for one second, and
6-25