HP-UX UPS Monitor Error Messages

Exit ups_mond Daemon Messages

Exit ups_mond Daemon Messages
The messages in this section precede the exiting of the ups_mond daemon. After the
appearance of one of these messages, the UPS Monitor will not be running, thus the
affected PowerTrust unit(s) will not be monitored.
MESSAGE
usage: ups_mond [-f configfile] [-s]
SEVERITY
Error.
MEANING
Incorrect parameter when invoking ups_mond.
CAUSE
An incorrect parameter was used when invoking ups_mond.
ACTION
Correct the parameter according to the syntax shown in the usage message
above. If ups_mond was invoked from /etc/inittab, edit that file to correct
the parameter.
MESSAGE
ups_mond: cannot exec ups_mond -f <filename> -e ups_monchild
due to <error number>
SEVERITY
Error.
MEANING
Cannot execute ups_mond's child process.
CAUSE
Specific cause denoted by <error number> in the message.
ACTION
Ensure that ups_mond exists in the /usr/bin directory, and is executable.