Fastening To The Ground; Installing The Control Unit - Kessel Aqualift F XL Mono Installation And Operating Manual

Lifting stations
Hide thumbs Also See for Aqualift F XL Mono:
Table of Contents

Advertisement

Available languages

Available languages

4.2.4

Fastening to the ground

Only use the bolts <36> provided for fastening the fixing
bracket <37> on the wastewater container. Using other screws
may lead to leaks in the container.
• Fasten the fixing bracket to the four
container.
• Attach the fixing bracket using the supplied fastening
material (7) to the ground (tensile strength min. 0.9 kN*).
* Bolts delivered with the station are designed for concrete flooring
(B25, tensile strength 0.9 kN)
4.3

Installing the control unit

• Install the control unit according to the operating and maintenance manual. When doing this, attach the
electrical connections of the pump(s) and the pressure sensor connector (or additional level detectors) to the
control unit.
The connection lengths (cable, pressure pipe) can be extended as follows:
Float switch and level sensor
Pressure sensor
Pump(s)
1)
After consultation with KESSEL 30 m
After initialisation, enter the station parameters as follows:
Control unit KESSEL Aqualift F Comfort 230V
- Aqualift type: Lifting station F XL xxx l (xxx = container volume)
- Pump type: According to delivery note
Control unit KESSEL Aqualift F Comfort 400V
Select the appropriate station in menu 3.6 performance size.
If this is not present, select custom station as follows:
For pump type
SPF 1500
SPF 3000
SPF 4500 or SPF 5500
Following this, set the parameters in the following table and/or check the settings.
1)
Two points for KESSEL Aqualift F XL 200 lifting station
Assembly
1
points on the wastewater
Standard
Extendible to
5 m
5 m
5 m
Setting in menu 3.6 performance size
Cust. pump <4A
Cust. pump <6.3A
Cust. pump <10.0A
44 / 60
[12]
15 m
1
15 m
30 m
37
7
36
V 1.0

Advertisement

Chapters

Table of Contents
loading

Table of Contents