[ALARM] / Troubleshooting menu
Alarm: Temperature difference is too
small.
Alarm: The cell temperature (internal)
is too low.
Alarm: The cell temperature (internal)
is too high.

8.1.4 Alarm: Product storage tank

Alarm: Level storage tank too low
Alarm: Liquid level of the degasser is
too high
Alarm: Degasser storage tank: impos‐
sible float situation.

8.1.5 Alarm: External product storage tank

Alarm: Liquid level of the external
product storage tank too low
34
This alarm occurs if there is too low a temperature difference. The
following causes are possible:
The temperature at the installation place is too low.
n
The process water temperature is too low.
n
This alarm occurs if the temperature at the inlet of one of the elec‐
trolysis cells is too low. The following causes are possible:
The process water temperature is too low.
n
This alarm occurs if the temperature at the inlet of one of the elec‐
trolysis cells is too high. The following causes are possible:
The process water temperature is too high.
n
This alarm occurs if the liquid level in the product storage tank is
too low. The following causes are possible:
More is pumped out of the product storage tank than is pro‐
n
duced by the system.
There is no production but chlorine is being consumed.
n
The level switch in the product storage tank is not working cor‐
n
rectly.
This alarm occurs if the liquid level in the degasser reaches the
switch. The following causes are possible:
The level switch in the degasser is not working correctly.
n
The degasser storage tank is filled with external liquids.
n
The control valve for softened water no longer closes.
n
This alarm occurs if the liquid level in the degasser reaches the
high-high float. The following causes are possible:
The degasser is filled with external liquids.
n
The control valve for softened water no longer closes.
n
The level switch in the internal product storage tank is not
n
working properly.
The system is producing more chlorine than is being pumped
n
out of the degasser.
This alarm occurs if the liquid level in the external product storage
tank is too low. The following causes are possible:
The level switch in the external product storage tank is not
n
working correctly.
More chlorine is pumped from the degasser than is produced
n
by the system.
No chlorine is produced but chlorine is being consumed.
n