Siemens Simovert Masterdrives Compact Plus Series Operating Instructions Manual page 279

Motion control frequency inverter (dc-ac)
Table of Contents

Advertisement

Available languages

Available languages

Faults and Alarms
Number / Alarm
Cause
A053
In a peer-to-peer connection, the pcD length of
transmitter and receiver do not match.
Peer Lng f.
not Compact PLUS
A057
Occurs when a TB is logged on and present,
but parameter tasks from the PMU, SCom1 or
TB Param
SCom2 have not been answered by the TB
within 6 seconds.
not Compact PLUS
A061
An active signal is present at binector U065
(1).
Alarm 1
Function blocks
A062
An active signal is present at binector U066
(1).
Alarm 2
Function blocks
A063
An active signal is present at binector U067
(1).
Alarm 3
Function blocks
A064
An active signal is present at binector U068
(1).
Alarm 4
Function blocks
A072
Automatic initiation of the friction characteristic
has been selected, but the drive has not yet
Frict Char Init
been switched on.
Note: If the ON command is not given within
30 seconds, the automatic initiation of the
friction characteristic is stopped with fault
F099.
A073
Automatic initiation of the friction characteristic
has been interrupted (OFF command or fault).
Interr InitFric
Note:
If the drive is not switched on again within 5
minutes, the automatic initiation of the friction
characteristic is stopped (F099).
A074
Incomplete initiation of friction characteristic.
As there is a lack of enables or due to
Incompl FricChar
limitations, complete initiation of the friction
characteristic is not possible in both directions.
A075
The measured values of the leakage
measurement or of rotor resistance deviate
Ls,Rr Dev.
significantly.
A078
The standstill measurement is executed when
the converter is powered up. The motor can
Stands. Meas
align itself several times in a certain direction
with this measurement.
A081
The following description refers to the 1st
CBP. For other CBs or the TB see operating
CB alarm
instructions for CB board.
The ID byte combinations which are being
sent from the DP master in the configuration
telegram are not in conformance with the
permissible ID byte combinations. (See also
Compendium, Chapter 8, Table 8.2-12).
Consequence:
No connection is made with the PROFIBUS
master.
12-16
Counter-measure
Adjust the word length for transmitter and
receiver
P703 SCom/SCB PcD #
Replace TB configuration (software)
Check cause of alarm (see FD 710)
Check cause of alarm (see FD 710)
Check cause of alarm (see FD 710)
Check cause of alarm (see FD 710)
Energize drive.
(Drive status "Operation" 014)
Rectifiy any causes of the fault.
Re-energize the drive.
Grant enable for both directions of rotation.
Set the speed limitations for both directions
such that all characteristic points can be
approached.
If individual measured values significantly
deviate from the average values, they are
automatically disregarded in the calculation
(for RI) or the value of the automatic
parameterization remains (for Ls).
It is only necessary to check the results for
their plausibility in the case of drives with high
requirements on torque or speed accuracy.
If the standstill measurement can be executed
without any danger:
- Power up the converter.
New configuration necessary
6SE7087-6KP50
Operating Instructions
SIMOVERT MASTERDRIVES
06.2006
Siemens AG

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents