Emerson Mentor MP Advanced User's Manual page 122

High performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Hide thumbs Also See for Mentor MP:
Table of Contents

Advertisement

Parameter
Menu 10
structure
10.20
Trip 0
10.21
Trip 1
10.22
Trip 2
10.23
Trip 3
10.24
Trip 4
10.25
Trip 5
10.26
Trip 6
10.27
Trip 7
10.28
Trip 8
10.29
Trip 9
Bit
SP
Coding
Range
0 to 229
Update rate
Background write
Contains the last 10 drive trips. Pr 10.20 is the most recent trip and Pr 10.29 the oldest. When a new trip occurs all the parameters move down one,
the current trip is put in Pr 10.20 and the oldest trip is lost from the bottom of the log. Descriptions of the trips are given in the table below. All trips are
stored, including HF trips numbered from 20 to 29. (HF trips with numbers from 1 to 16 are not stored in the trip log.) Any trip can be initiated by the
actions described or by writing the relevant trip number to Pr 10.38. If any trips shown as user trips are initiated the trip string is "txxx", where xxx is
the trip number.
Table 5-4 Trip indications
No.
String
Cause of trip
1
UU
Running from external +24V
2
t002
Reserved
3
AOC
An instantaneous over current in the armature circuit
4
t004
Reserved
5
PS
Internal drive power supply trip
6
Et
External trip (see Pr 10.32)
7
O.SPd
Overspeed
8
PS.10V
10V user power supply overload
9
PS.24V
24V internal power supply overload
10
t010
User trip
11
tunE1
The position feedback did not change or required speed could not be reached during the inertia test (see Pr 5.12)
12
tunE2
Position feedback direction incorrect or motor could not be stopped during the inertia test (see Pr 5.12)
13
tunE3
Field flux has not reached zero during autotune
14
tunE4
Back emf detected during autotune
15
tunE5
No field current detected detected during autotune
16
tunE6
Cannot achieve 1/4 rated back emf during autotune. Reset Pr 5.70 to nameplate value and repeat autotune
17
tunE7
Rotated autotune initiated with Estimated speed selected
18
tunE
Autotune stopped before completion (see Pr 5.12)
19
t019
Reserved
20
It.AC
2
I
21
O.ht1
Drive overheat (thyristor junction) based on thermal model
22
O.ht2
Drive over-heat based on heatsink temperature (see Pr 7.04)
23
t023
User trip
24
Th
Motor thermistor trip (see Pr 7.11)
25
ThS
Motor thermistor short circuit (see Pr 7.11)
26
O.Ld1
Digital output overload
27
O.ht3
Extend discharge resistor over temperature
28
cL2
Analog input 2 current mode: current loss (see Pr 7.11)
122
Keypad and
Parameter x.00
display
FI
DE
Txt VM DP
ND
1
1
t on drive output current (see Pr 4.15)
www.controltechniques.com
Parameter description
Advanced parameter
format
RA NC NV
PT
US RW BU
1
1
Serial comms
descriptions
protocol
PS
1
1
Mentor MP Advanced User Guide
Performance
Issue Number: 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents