The trip log includes time stamping for individual trips provided Pr 6.49 =1.
If Pr 6.28 = 0, the powered-up clock is used for time stamping.
If Pr 6.28 = 1, the run time clock is used for time stamping.
It should be noted that changing this parameter clears the trip and trip time logs.
6.29
Hardware enable
Bit
SP
Coding
1
Update rate
4ms write
This bit shows whether the drive is in the enable state or not.
Generally this will reflect the state of the enable input and shows the same value as Pr 8.09. However the disabled state can be forced by inputs
routed to this parameter. Pr 8.09 will always follow the enable input state but Pr 6.29 will be held at zero, indicating that the drive is forced into the