0 - the internal and external field controllers are disabled.
1 - the internal field controller is enabled. When the internal field controller is enabled then it will control Pr 5.56, Pr 5.57 and Pr 5.58.
2 - the external field controller is enabled. When the external field controller is enabled then it will control Pr 5.54 and Pr 5.56. If no signal is received
from the external field controller the drive will trip field loss.
Full control enable
5.78
Bit
SP
Coding
1
Range
0 to 1
0
Default
Background read
Update rate
Provides the option for a fully controlled bridge when using the external field controller.
Economy active
5.79
Bit
SP
Coding
1
Range
0 to 1
0
Default
Background read
Update rate
When this bit is set the economy timeout feature is selected.
Economy level select
5.80
Bit
SP
Coding
1
Range
0 to 1
0
Default
Background read
Update rate
5.81
Field thermal time constant
Bit
SP
Coding
0.0 to 3000.0
Range
41.0
Default
21.30
Second motor
parameter
Background read
Update rate
The motor is modelled thermally in a way that is equivalent to the electrical circuit shown below.
τ = RC
2
2
I
/(1.05*Field Rated Current)
The temperature of the field as a percentage of maximum temperature, with a constant current magnitude of I and constant value of field rated current
(set by Pr 5.70 or Pr 21.24) after time t is given by