Default; Second Motor Parameter; Update Rate; Sources And Destinations - Emerson Mentor MP Advanced User's Manual

High performance dc drive 25a to 7400a, 480v to 690v two or four quadrant operation
Hide thumbs Also See for Mentor MP:
Table of Contents

Advertisement

Parameter structure
Keypad and display
Maximum
QUADRANT_MAX
POWER_MAX
[9999.99kW]
The values given in square brackets indicate the absolute maximum value allowed for the variable maximum.
4.1.1

Default

The default values given are the standard drive defaults which are
loaded after a drive reset with Eur or USA in Pr x.00.
4.1.2

Second motor parameter

Some parameters have an equivalent second motor value that can be
used as an alternative when the second motor is selected with Pr 11.45.
Menu 21 contains all the second motor parameters. In this menu the
parameter specifications include the location of the normal motor
parameter which is being duplicated.
4.1.3

Update rate

Defines the rate at which the parameter data is written by the drive
(write) or read and acted upon by the drive (read). Where background
update rate is specified, the update time depends on the drive processor
load. Generally the update time is between 2ms and 30ms, however, the
update time is significantly extended when loading defaults, changing
drive mode, transferring data to/from a SMARTCARD, or transferring
blocks of parameters or large CMP data blocks to/from the drive (not a
Solutions Module) via the drive serial comms port.
4.2

Sources and destinations

4.2.1

Sources

Some functions have source pointer parameters, i.e. drive outputs, PID
controller etc.. The source pointer parameter range is Pr 0.00 to
Pr 22.99 The source pointer is set up to point to a parameter, which
supplies the information to control the source and this is referred to as
the source data parameter. For example, Pr 7.19 is the source pointer
parameter for analog output 1. If Pr 7.19 is set to a value of 18.11, then
Pr 18.11 is the source data parameter, and as the value of Pr 18.11 is
modified the analog output level is changed.
1. If the parameter number in the source pointer parameter does not
exist the input is taken as zero.
2. If the source is not a bit type source (i.e. not a digital output etc.)
then the source level is defined by (source data value x 100%) /
source data parameter maximum. Generally the result is rounded
down to the nearest unit, but other rounding effects may occur
depending on the internal scaling of the particular source function.
3. If the source is a bit, i.e. a digital output, and the source data
parameter is a bit parameter then the input to the source function
follows the value of the source data parameter.
4. If the source is a bit, i.e. a digital output, and the source data
parameter is not a bit parameter the source input is zero if the
source data value is less than source data parameter maximum / 2
rounded down to the nearest unit. The source input is one if the
source data value is greater than or equal to source data parameter
maximum / 2 rounded down to the nearest unit. For example if the
source pointer parameter is set to 18.11, which has a maximum of
32767, the source input is zero if the source data value is less than
16383 and one if it is greater than this.
4.2.2

Destinations

Some functions have destination pointer parameters, i.e. drive inputs,
etc.. The destination pointer parameter range is P 0.00 to Pr 22.99. The
destination pointer parameter is set up to point to a parameter, which
receives information from the function referred to as the destination
parameter.
Mentor MP Advanced User Guide
Issue Number: 1
Parameter description
Parameter x.00
format
Quadrant maximum
0 for a 2 quadrant drive.
1 for a 4 quadrant drive.
Maximum power in kW
The maximum power has been chosen to allow for the maximum power that can be output by the drive with
maximum DC output voltage and maximum controlled current.
Therefore:
POWER_MAX = ARMATURE_VOLTAGE_MAX x DRIVE_CURRENT_MAX
www.controltechniques.com
Advanced parameter
descriptions
Definition
1. If the parameter number in the destination pointer parameter does
not exist then the output value has no effect.
2. If the destination parameter is protected then the output value has
no effect.
3. If the function output is a bit value (i.e. a digital input) the destination
parameter value does not operate in the same way as a source
described above, but is always either 0 or 1 depending on the state
of the function output whether the destination parameter is a bit
parameter or not.
4. If the function output is not a bit value (i.e. analog input) and the
destination parameter is not a bit parameter, the destination value is
given by (function output x destination parameter maximum) / 100%.
Generally the result is rounded down to the nearest unit, but other
rounding effects may occur depending on the internal scaling of the
particular source function (rounded down to nearest unit). Pr 1.36
and Pr 1.37 are a special case. The scaling shown in the description
of parameter Pr 1.08 is used when any non-bit type quantity is
routed to these parameters.
5. If the function output is not a bit value and the destination parameter
is a bit value, the destination value is 0 if the function output is less
than 50% of its maximum value, otherwise it is 1.
6. If more than one destination selector is routed to the same
destination, the value of the destination parameter is undefined. The
drive checks for this condition where the destinations are defined in
any menu except menus 15 to 17. If a conflict occurs a dESt trip
occurs that cannot be reset until the conflict is resolved.
4.2.3
Sources and destinations
1. Bit and non-bit parameters may be connected to each other as
sources or destinations. The scaling is as described previously.
2. All new source and destination routing only changes to new set-up
locations when the drive is reset.
3. When a destination pointer parameter within the drive or a dumb
option module (SM-Resolver, SM-Encoder Plus, SM-I/O plus) is
changed the old destination is written to zero, unless the destination
change is the result of loading defaults or transferring parameters
from a SMARTCARD. When defaults are loaded the old destination
is set to its default value. When parameters are loaded from a
SMARTCARD the old destination retains its old value unless a
SMARTCARD value is written to it.
Serial comms
Performance
protocol
19