Indicates that power is being transferred from the motor to the supply.
10.13
Direction commanded
Bit
SP
Coding
1
Update rate
Background write
This parameter is one if the pre-ramp reference (Pr 1.03) is negative, and zero if the pre-ramp reference is zero or positive.
10.14
Direction running
Bit
SP
Coding
1
Update rate
Background write
This parameter is one if the speed feedback (Pr 3.02) is negative, or zero if the speed feedback is zero or positive.
10.17
Overload alarm
Bit
SP
Coding
1
Update rate
Background write
This parameter is set if the drive output current is larger than 105% of rated current (Pr 5.07) and the overload accumulator is greater than 75% to
warn that if the motor current is not reduced the drive will trip on an Ixt overload. (If the rated current (Pr 5.07) is set to a level above the rated drive
current (Pr 11.32) the overload alarm is given when the current is higher than 100% of rated current.)
10.18
Drive over temperature alarm
Bit
SP
Coding
1
Update rate
Background write
Indicates that the heat sink temperature Pr 7.04 is above the alarm level.
10.19
Drive warning
Bit
SP
Coding
1
Update rate
Background write
Indicates that one of the drive alarms is active, i.e. Pr 10.19 = Pr 10.17 OR Pr 10.18.