Defined as the voltage at which base speed is reached.
This should be set to the value of the armature back emf at which field weakening is required to start.
5.61
Armature Resistance
Bit
SP
Coding
0 to 6.0000 Ohms
Range
0
Default
Second motor
Pr 21.10
parameter
Update rate
Background read
This is used to calculate the armature IR voltage drop that is used as a correction to the measured armature voltage, to allow the back emf to be
computed.
5.62
Spill over loop P gain
Bit
SP
Coding
0 to 300.00
Range
0.4
Default
Update rate
Background read
Spill over loop I gain
5.63
Bit
SP
Coding
0 to 300.00
Range
5
Default
Update rate
Background read
Enable economy timeout
5.65
Bit
SP
Coding
1
0 to 1
Range
Update rate
0 Eur 1 USA
Permits the field current to be configured to the field economy level (Pr 5.67) automatically after the drive has been disabled for a period of time (Pr
5.64). This is used to prevent the motor windings from overheating if the drive is stopped, and the motor ventilation is switched off. This can also be
used to prevent condensation in the motor when it is not in use.
5.67
Field economy level
Bit
SP
Coding
0 to 200.0%
Range
25%
Default
Update rate
Background read
Sets the reduced field current level used when the field economy function is used.