Self testing non-maintained emergency ceiling mounted luminaires

Advertisement

battery fault led turns on continuously indicating
that the battery must be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the list of the technical characteristics.
During emergency mode, a light source test is
also performed.
Resetting Errors
Push the Test button for >10 seconds, to delete
all the indicated LED errors. Then the device
enters regular operation mode.
Test Switch
Pressing the test switch less than 5 seconds
will initiate a light source test (last for 3 secs).
If the test switch is pressed for more than 10
seconds, the device will be reset (delete all
errors).
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation or maintainance
must be done by authorized personnel only.
2. The device must be connected to the mains
power supply through a fuse dependent by the
total amount of the line's power load.
3. The replacement of the battery and the light
source must be done using parts of the same
type, by the manufacturer or by a competent
person.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery's connector.
5. I s not allowed to discard batteries into
t i
common trash bins, they must be
discarded only
points. Do not incinerate.
LEDs
CHARGE
LAMP FAULT
BATT. FAULT
Note
Page 2 from 6
in battery recycling
Status of LEDs
Description of indication
: Battery charging,
: battery charged,
: Operation check,
: lamp fault,
: Autonomy test,
: autonomy fault,
: Blinking,
: constantly on,
Connection to module (After request)
This luminaire can be connected to any of the
following modules: Remote module, address
module, wireless module and fault relay
module. If you connect it to a module that
supports inhibit or rest mode, you should know
that these commands can be cancelled only
during normal mode (ie. not in emergency). For
installation refer to step 2 of the istallation
procedure in page 3.
Also refer to the user's manual of each module
for additional information.
NOTE: LED= Light Emitting Diode

LABELING EXPLANATION:

X: Self contained
0: Non maintained (*)
A: Including test device
F: Automatic test gear complying with IEC
61347-2-7 denoted EL-T
180: 3 hour duration
Maintained operation: The luminaire lights its
illumination source, when it is powered by the
mains power supply or not.
(*) Non Maintained operation: The luminaire
turns on illumination source, only in case of
power supply failure.
Note!! If a module will be used (except the fault
relay module), then the installer should fill in, on
the specification label, the letters B C.
: disconnected battery
: normal operation
: normal operation
: off
X 0 A F
1
8 0
923293007_09_001