Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated
in
the
characteristics. During emergency mode, a
light source test is also performed.
Resetting Errors
Push the Test button for >10 seconds, to
delete all the indicated LED errors. Then the
device enters regular operation mode.
Test Switch
Pressing the test switch less than 5 seconds
will initiate a light source test (last for 3 secs).
If the test switch is pressed for more than 10
seconds, the device will be reset (delete all
errors).
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. The device must be connected to the
m a i n s p o w e r s u p p l y t h r o u g h a f u s e
dependent by the total amount of the line's
power load.
3. The replacement of the battery and the light
source must be done using parts of the same
type, by the manufacturer or by a competent
person.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery's connector.
5. I s not allowed to discard batteries into
t i
common trash bins, they must be
discarded only
points. Do not incinerate.
LEDs
CHARGE
LAMP FAULT
BATT. FAULT
Note
Page 2 from 6
list
of
the
technical
in battery recycling
Status of LEDs
Description of indication
: Battery charging,
: battery charged,
: Operation check,
: lamp fault,
: Autonomy test,
: battery fault,
: Blinking,
: constantly on,
NOTE: LED= Light Emitting Diode

LABELING EXPLANATION:

X: Self contained
0: Non maintained (*)
A: Including test device
F: Automatic test gear complying with IEC
61347-2-7 denoted EL-T
90: 1.5 hour duration
180: 3 hour duration
X 0
A F
9 0
(*) Non Maintained operation: The luminaire
turns on illumination source, only in case of
power supply failure.
: disconnected or unfunctional battery
: normal operation
: normal operation
: off