Download Print this page

Labeling Explanation - olympia electronics GR-939/30L/LT Quick Start Manual

Waterproof self testing maintained emergency luminaires

Advertisement

user that the battery must be replaced.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the illumination sign's back up
operation and emergency duration. This test is
conducted automatically every six months. In
order to be performed, the mains power supply
and the battery should be connected and fully
charged. If the battery is not fully charged, the
test
is
postponed
completely charged. If during the Automatic
Autonomous Test the luminaire's duration is
lower than the nominal, then the battery must
be replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated
in
the
characteristics. During emergency mode, a
LED strip test is also performed.
Resetting Errors
Push continuously the TEST/RESET button for
>10 seconds, to delete all the indicated LED
errors . Then
the luminaire enters regular
operation mode.
Test Switch (Briefly)
Pressing the test switch less than 5 seconds
will initiate a light source test (last for 3 secs).
Pressing the test switch between 5 to 10
seconds will initiate a manual battery duration
test. This test will not be started if the battery
is not fully charged (i.e. If the green LED is
flashing). If the test switch is pressed for more
than 10 seconds, the device will
errors).
NOTE: LED= Light Emitting Diode

LABELING EXPLANATION:

X: Self contained
1: Maintained (*)
A: Including test device
G: Internally illuminated
*90: 1.5 hour duration
180: 3 hours duration
(*) Non Maintained operation: The luminaire lights its illumination source, only in power supply's
failure.
Maintained operation: The luminaire lights its illumination source, when it is powered by the mains
power supply or not.
Page 2 from 5
until
the
battery
list
of
the
technical
delete all
Note!! The installer should fill in, on the specification label,
the letter G if the luminaire is used as a safety sign.
X 1
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. The device must be connected to the mains
power supply through a fuse dependent by the
total amount of the line's power load.
3.
In case of battery or lamp replacement, these
must be replaced by parts of the same type, by
is
the manufacturer or by a competent person.
4. In case of inactive use for a period
greater than 2 months, disconnect the
battery by pulling out the battery's
connector.
5. I s not allowed to discard batteries in to
t i
common trash bins, they must be discarded
only
in battery recycling points. Do not
incinerate.
Battery Replacement
1. Unfasten the 4 retaining screws (step 8 of the
installation instructions) and remove the
diffusor.
2. Unfasten the 2 retaining screws step 7 of the
installation instructions and remove the
reflector.
3. Remove the old battery and place a new on
of the same type and characteristics.
4. Replace the removed parts (previous steps
1,2).
Important notice for the installed luminaires
in one area !!!
The installer must connect the battery's
connector first and then should power the
luminaire. The batteries connection must have at
least a time variation of 1.5 minute for each
luminaire. With this variation, it is ensured that the
non synchronized Automatic Autonomous Test
for two or more luminaires installed in one area, is
not conducted in the same day.
A G