Motor Connection - Siemens PM330 Hardware Installation Manual

Sinamics g120p power module
Table of Contents

Advertisement

Table 4- 3
Cable used
Shielded cable, devices without
output filter
Unshielded cable, devices without
output filter
Shielded cable, devices with out-
put filter
Unshielded cable, devices with
output filter
4.2.4

Motor connection

Star and delta connection
Siemens motors have a diagram inside the
terminal box showing both connection meth-
ods:
• Star connection (Y)
• Delta connection (Δ)
The motor rating plate provides data about the
correct connection.
Connecting the motor to the converter
Connect the protective conductor of the motor to the
Connect the motor cable to terminals U2, V2 and W2.
If available, close the terminal covers of the converter.
Power Module PM330
Hardware Installation Manual, 12/2018, A5E32844552B AF
Maximum cable lengths
Maximum cable lengths
150 m
200 m
300 m
100 m
450 m
150 m
Connecting up, switching on
4.2 Line, motor and DC link connection
Output filter
--
--
Output reactor, du/dt filter
du/dt filter compact
Output reactor, du/dt filter
du/dt filter compact
terminal of the converter.
35