Siemens PM330 Hardware Installation Manual page 104

Sinamics g120p power module
Table of Contents

Advertisement

Technical specifications
6.3 Derating data
Decreasing the ambient temperature and the output current
The permissible output currents as a function of the installation altitude and ambient
temperature are listed in the following tables.
Due to the reduced cooling efficiency as the altitude increases, it is necessary, on the one
hand, to reduce the ambient temperature and, on the other, to reduce the power loss of the
Power Module by reducing the output current, whereby ambient temperatures lower than
45 °C may be taken into consideration to compensate, and are taken into account in the
tables. The values apply under the precondition that a cooling air flow through the devices is
ensured as specified in the technical specifications.
Table 6- 8
Current derating as a function of the ambient temperature and installation altitude for frame size GX
Installation altitude
above mean sea
level in m
20 °C
0 ... 1000
100%
1001 ... 1500
100%
1501 ... 2000
100%
2001 ... 2500
100%
2501 ... 3000
100%
3001 ... 3500
100%
3500 ... 4000
100%
Table 6- 9
Current derating as a function of the ambient temperature and installation altitude for frame sizes HX and JX
Installation altitude
above mean sea
level in m
20 °C
0 ... 1000
100%
1001 ... 1500
100%
1501 ... 2000
100%
2001 ... 2500
100%
2501 ... 3000
100%
3001 ... 3500
100%
3500 ... 4000
100%
102
Current derating factor

 a t an ambient temperature (air intake temperature) of
25 °C
30 °C
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
97%
98%
92%
Current derating factor

 a t an ambient temperature (air intake temperature) of
25 °C
30 °C
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
98%
35 °C
40 °C
100%
100%
100%
100%
100%
99%
100%
94%
96%
90%
91%
85%
86%
81%
35 °C
40 °C
100%
100%
100%
100%
100%
100%
100%
97%
100%
94%
96%
90%
92%
86%
Hardware Installation Manual, 12/2018, A5E32844552B AF
45 °C
50 °C
100%
93%
96%
89%
92%
85%
88%
81%
83%
77%
79%
73%
75 %
69%
45 °C
50 °C
100%
93%
97%
89%
93%
86%
90%
83%
87%
80%
84%
77%
80%
74%
Power Module PM330
55 °C
85%
81%
78%
74%
71%
67%
64%
55 °C
85%
82%
79%
76%
74%
71%
68%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents