Siemens PM330 Hardware Installation Manual page 95

Sinamics g120p power module
Table of Contents

Advertisement

Article No.
Recommended cable cross-section for 480 V
- DC link infeed (2/3 inverter power)
- Braking Module
4)
Tightening torque for line, motor, DC link, and
ground cable
Dimensions: Width x height x depth [mm]
Weight
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
1)
tial damage is avoided.
Note: If the minimum short-circuit current is not reached, then the tripping time for the fuses increases, and this may re-
sult in consequential damage.
When semiconductor fuses are used, they must be mounted in the same higher construction as the inverter.
2)
The motor cables must be evenly distributed at both connection chambers.
3)
For connection of the Braking Module with rated power of 50 kW, P
4)
Power Module PM330
Hardware Installation Manual, 12/2018, A5E32844552B AF
6SL3310-
1PE38-4AA0
3 x 120 mm
35 mm²
50 Nm / 443 lbf in
801 x 1621 x 393
235 kg
6.2 Specific technical data
1PE38-8AA0
3 x 150 mm
2
2
35 mm²
50 Nm / 443 lbf in
801 x 1621 x 393
250 kg
power of 200 kW.
20
Technical specifications
1PE41-0AA0
3 x 185 mm
2
35 mm²
50 Nm / 443 lbf in
801 x 1621 x 393
250 kg
93