Advertisement

Connecting up, switching on
4.6 Terminal block X41 / switch S41
4.6.1

Terminal strip X41

Terminal strip X41
Table 4- 4
Terminal strip X41
Terminal Name
1
STO_A1
2
STO_AM
3
STO_B1
4
STO_BM
5
FB_A1
6
FB_A2
7
FB_B1
8
FB_B2
Maximum connection cross section: 1.5 mm²
Minimum connection cross section: 0.2 mm²
Maximum tightening torque: 0.22 Nm (1.9 lbf in)
Control cable capacitance
Maximum control cable capacitance: 330 pF/m
Insulated end sleeves
Insulated end sleeves according to DIN 46228-4 must be used.
Strain relief
For strain relief, the cables to the Control Unit and to the terminal X41 must be fastened to
the lugs in the cable duct below terminal X9 (e.g. with cable ties).
If the cables are introduced at the side (at the height of terminal X9), the strain relief must be
provided outside the Power Module.
52
Meaning
STO control, channel A
Reference ground for
input STO_A1
STO control, channel B
Reference ground for
input STO_B1
Feedback signal contact
diagnostics channel A
Feedback signal contact
diagnostics channel B
Input/
Technical data
output
Input
Voltage: -3 V ... +30 V
Signal level (including ripple):
Reference
High signal level: 15 V ... 30 V -> STO deselected (op-
Input
eration possible)
Reference
Low signal level: -3 V ... +5 V -> STO active (operation
inhibited)
Current consumption:
2 mA at <15 V
15 mA at 30 V
15 mA at 24 V
Floating
Voltage: -3 V ... +30 V
contact
Max. current for a resistive load: 500 mA
Floating
Voltage: -3 V ... +30 V
contact
Max. current for a resistive load: 500 mA
Hardware Installation Manual, 12/2018, A5E32844552B AF
Power Module PM330