Jet Deflector - Deif Multi-line 2 Description Of Options

Option o1 water turbine control
Table of Contents

Advertisement

GPC, PPU
In principle, the jet deflector is a 3-way valve intended to bypass the water flow in case there is a
generator shutdown.
Principle
Normally, the jet deflector is 'closed' (water flow led to the turbine) and held closed by a holding
magnet. In case of shutdown, the jet deflector magnet is deactivated, and the jet deflector
immediately changes to 'open' (water bypass) position.
The principle looks like this (jet deflector shown in 'closed' position):
Closed position
Water inlet
Open position
If the jet deflector is moved to the 'open' position, it must be set back to 'closed'
position manually.
Use the jet deflector feedback to indicate when the deflector is closed.
Relay selection
The relay used for the jet deflector is the relay 1. (Terminal 5, 6, 7 - see extract from I/O list
below).
Term.
Function
5
NO
6
Com.
7
NC
DEIF A/S

Jet deflector

Jet deflector
Moving
weight
Technical
Description
data
Relay 1
Configurable/jet deflector operation
250V AC / 8A
Option O1, Water turbine control
Holding
magnet
bypass
To turbine
Page 12 of 19