Chapter 2 Installing The Frame-Mounted Tracer Mp581; Enclosure Requirements - Trane Tracer MP581 Hardware Installation

Hide thumbs Also See for Tracer MP581:
Table of Contents

Advertisement

CNT-SVN01C-EN
Chapter 2
Installing the frame-mounted
Tracer MP581
This chapter applies only to the frame-mounted Tracer MP581 controller.
You can use the frame-mounted Tracer MP581 to replace older controllers
in existing equipment or to mount in new equipment or custom
enclosures.

Enclosure requirements

Before installing the frame-mounted Tracer MP581, make sure that the
enclosure or mounting space meets the following minimum requirements:
Minimum clearances as shown in Figure 3
24 Vac dedicated power supply
Compliance with National Electrical Code and applicable local elec-
trical codes for high-voltage power wiring to the enclosure
Note:
The Tracer MP581 with enclosure is mounted in a National
Electrical Manufacturers Association (NEMA) 1 enclosure. To
meet NEMA 4 specifications, you can order the frame-mounted
Tracer MP581 (model BMTM000CA0A0) and mount it in a
separately purchased NEMA 4 enclosure.
Figure 3. Frame-mounted Tracer MP581 minimum clearances
6 in. (152 mm)
for I/O wires
0.5 in. (13 mm)
0.5 in. (13 mm)
3 in. (76 mm)
for communications wires
0.5 in.
(13 mm)
7