Table 30. Voltage measurements at universal inputs (no sensor connected)
Input type
Thermistor
Binary
Current
Voltage
92
Expected value
5.00 Vdc
17.00 Vdc
0.116 Vdc
3.43 Vdc
Acceptable range
4.75 to 5.25 Vdc
16.00 to 18.00 Vdc
0.100 to 0.130 Vdc
3.10 to 3.80 Vdc