Checking The Pressure Sensor - Trane Tracer MP581 Hardware Installation

Hide thumbs Also See for Tracer MP581:
Table of Contents

Advertisement

CNT-SVN01C-EN

Checking the pressure sensor

You can check the pressure sensor for proper operation only after supply-
ing power to the controller and installing the main circuit board. You will
need a digital multi-meter to complete the check.
To check the pressure sensor for proper operation:
1. Make sure that the main circuit board has been installed and power
has been provided to the controller.
2. Make sure that the pressure-sensor is connected to the duct-static
input on the termination board.
3. Set the digital multi-meter to measure dc voltage.
4. Connect the multi-meter to the input as shown in Figure 20 and dis-
cussed in table Table 7.
Figure 20. Connecting the multi-meter to the duct-static input
5. Make sure that the multi-meter readings fall within the ranges
shown in Table 7. If a reading is not within the expected range, check
for faulty connections or a faulty pressure sensor.
Table 7. Expected voltages for the pressure sensor input
Multi-meter (–) lead at
Green (ground)
Green (ground)
Checking the pressure sensor
Green
Black
Red
Duct-static connector
on termination board
Multi-meter (+) lead at
Red (in)
Black (out)
Measured dc voltage
4.8–5.2 Vdc
0.24–5.2 Vdc
37