Trane Tracer MP581 Hardware Installation page 53

Hide thumbs Also See for Tracer MP581:
Table of Contents

Advertisement

Figure 23. Daisy chain resistor placement
System panel
Figure Note:
105 Ω, 1%, 1/4 Watt for 22 AWG, Level 4
82 Ω, 1%, 1/4 Watt for 18 AWG, Trane "purple' wire
Figure 24. Alternate daisy chain resistor placement
Termination
resistor
Device
Figure Note:
Maximum wire length for the entire configuration Comm5 is 4,500 ft (1,400 m)
Maximum wire length for Comm5 is 4,500 ft (1,400 m) (Comm5 wire length
limitations can be extended through the use of a link repeater, see "Comm5
physical link repeater" on page 44)
CNT-SVN01C-EN
Termination resistor
Device
Device
Termination
resistor
Repeater
Device
System panel
Termination resistance placement for Comm5 links
Device
Termination
resistor
Device
Device
Device
Termination
resistor
Termination
resistor
Device
43

Hide quick links:

Advertisement

Table of Contents
loading