Chapter 3
Mounting the enclosure
This chapter describes location requirements and shows how to mount
the Tracer MP581 enclosure.

Selecting a mounting location

Make sure that the location meets the operating environment require-
ments and clearance requirements described in the following sections.
The Tracer MP581 controller must be installed indoors. Trane recom-
mends locating the Tracer MP581 controller:
Near the controlled equipment to reduce wiring costs
Where service personnel have easy access
Where it is easy to see and interact with the operator display
Where public access is restricted to minimize the possibility of
tampering or vandalism
CAUTION
Equipment damage!
Install the Tracer MP581 in a location that is out of direct sunlight. Fail-
ure to do so may cause the Tracer MP581 to overheat.

Operating environment requirements

Make sure that the operating environment conforms to the specifications
listed in Table 2.
Table 2. Operating environment specifications
Temperature
With enclosure: From 32°F to 122°F (0°C to 50°C)
Frame-mount (without enclosure): From –40°F to
158°F (–40°C to 70°C)
Humidity
10–90% non-condensing
Altitude
6500 ft (2000 m)
High-voltage power
North America: 98–132 Vac, 1 A maximum, 1 phase
requirements
Other: 196–264 Vac, 1 A maximum, 1 phase
Weight
Mounting surface must be able to support 25 lb (12 kg)
Note:
The Tracer MP581 with enclosure is mounted in a National
Electrical Manufacturers Association (NEMA) 1 enclosure. To
meet NEMA 4 specifications, you can order the frame-mounted
Tracer MP581 (model BMTM000CA0A0) and mount it in a
separately purchased NEMA 4 enclosure.