Wiring Analog Outputs - Trane Tracer MP581 Hardware Installation

Hide thumbs Also See for Tracer MP581:
Table of Contents

Advertisement

Figure 16. Wiring analog outputs
Ac powered actuator
24 Vac
Signal
Common
Tape back shield
Signal
Common
0–10 Vdc output
Load > 500 Ω
0–20 mA output
Load < 500 Ω
CNT-SVN01C-EN

Wiring analog outputs

The Tracer MP581 controller has six analog outputs. These outputs can
be either 0–10 Vdc outputs or 0–20 mA outputs. Analog outputs control
actuators and secondary controllers.
To wire an analog output:
1. For three-wire applications, use the shield wire as the common con-
nection (see Figure 16). For two-wire applications, connect the shield
wire to a common terminal at the termination board and tape it back
at the output device.
2. Connect the signal wire to an available analog output terminal
(AO1–AO6).
3. Connect the supply wire to a 24 Vac terminal as required.
4. Use the Rover service tool to configure the analog output.
< 1000 ft
(300 m)
< 1000 ft
(300 m)
< 300 ft
Signal
(100 m)
Tape back shield
Common
Wiring analog outputs