AUMA SA Series Operation Instructions Manual page 56

Multi-turn actuators
Hide thumbs Also See for SA Series:
Table of Contents

Advertisement

Commissioning (basic settings)
Select main menu
Select parameter
CLOSED or OPEN
User login
Set end position
CLOSED CMD0009
56
SA 07.2
SA 16.2/SAR 07.2
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
1.
Set selector switch to position 0 (OFF).
2.
Press push button C and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: ▶ Display...
3.
Select parameter either:
click via the menu
via direct display: press
Display indicates: Set end pos.CLOSED?
4.
Use
Up ▲ Down ▼ to select:
▶ Set end pos.CLOSED? M0084
▶ Set end pos. OPEN? M0085
The black triangle ▶ indicates the current selection.
5.
Ok.
Press
The display indicates either:
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 12
-
Specialist (4) → continue with step 6
6.
Up ▲ Down ▼ to select user:
Use
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
7.
Press
Ok to confirm to selected user.
Display indicates: Password 0***
8.
Enter password (→ enter password).
The display indicates either:
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 12
9.
Set again end position CLOSED:
9.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
9.2 Engage manual operation.
9.3 Turn handwheel until valve is closed.
9.4 Turn handwheel by approximately half a turn (overrun) in the opposite
direction of end position.
9.5 Set selector switch to position 0 (OFF).
Display indicates: Set end pos.CLOSED? Yes No
SAR 16.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive HART
to parameter, or
and enter ID M0084.
(CLOSE) in

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents