Technical Data - WAGO 750-643 Manual

I/o system 750 fieldbus independent i/o modules mp-bus master module
Table of Contents

Advertisement

2.1.1.5 Technical data

Module-specific data
MP-Bus specification
Maximum number of slaves
Supply voltage (MP-Bus)
Current consumption (MP-Bus)
Transmission rate
Programming
Diagnostic information
Error behavior
Supply voltage (internal)
Current consumption (internal)
Potential isolation
Data width internal
Dimensions W x H*
*
Weight
Norms and Directives (cf. Chapter 2.2 in manual for controller)
EMC CE Immunity
EMC CE Emissions
EMC marine applications
immunity to interference
EMC marine applications
emission of interference
Approvals (cf. Chapter 2.2 in manual for controller)
Accessories
Mini-WSB fast marking system
WAGO-I/O-SYSTEM 750
I/O Modules
)
x D
)
from top edge of mounting rail
UL
(UL508)
C
US
Conformity Marking
750-643 [MP-Bus Master Module]
Belimo PP/MP Specifications V1.21
(valid from 1.10.2002)
8
DC 24 V via power contacts
25 mA without motor current (for MP-Bus)
When the motors are supplied from the MP-Bus
module, the current values for all motors must be added
to this.
1200 bit/s
via WAGO-I/O-PRO
Error bits in status byte
Automatic restart on return of power
via system voltage DC/DC
15 mA
500 V System/MP-Bus
1 byte C/S, 7 bytes data
12 mm x 64 mm x 100 mm
55 g
according to EN 61000-6-2 (02), (EN 50082-2)
according to EN 61000-6-3 (04), (EN 50081-1)
according to Germanischer Lloyd (01) *
according to Germanischer Lloyd (01) *