Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 83

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

Comfort Link™ Compressor Protection Module Configuration Header Punch-Outs and Must Trip Amps
UNIT
VOLTS-Hz
30HXA
575-3-60
380-3-60
230-3-60
076
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
086
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
096
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
106
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
116
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
126
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
136
208/230-3-60
460-3-60
230-3-50
380/415-3-50
575-3-60
380-3-60
230-3-60
146
208/230-3-60
460-3-60
230-3-50
380/415-3-50
APPENDIX A (cont)
30HXA Models
PUNCHOUTS
PUNCHOUTS
FOR COMP
FOR COMP
A1
A2
1,2,3,4
1,2,4,5,7,8
1,3,4,7,8
1,3,5
1,2,3,6,7
1,3,5,6,7,8
1,2,4,5,8
1,2,3,5
1,2,5,6,7,8
1,4,5,6,7,8
1,4,7
1,2,4,5,6
1,4,5,8
1,2,5,7,8
1,2,4,5,6,8
1,3,4,5,6,7,8
1,6,8
2,3,4,6,8
1,2,5,6,7,8
2,3,4,5,6,7
1,3,4,5,7,8
1,2,4,8
1,3,5,6
2,3,6,8
2,4,8
1,3,4,5,6,7,8
2,4,5,6,8
1,3,6,7,8
1,2,4,8
1,3,5,6
2,3,6,8
2,4,8
1,3,4,5,6,7,8
2,4,5,6,8
1,3,6,7,8
1,2,4,8
1,3,5,6
2,3,6,8
2,4,8
1,3,4,5,6,7,8
2,4,5,6,8
1,3,6,7,8
1,2,8
1,4,6
3,4,5,6,7
3,6,7
1,3,5,7,8
3,4,7
1,5,6,8
1,2,8
1,4,6
3,4,5,6,7
3,6,7
1,3,5,7,8
3,4,7
1,5,6,8
COMP A1
PUNCHOUTS
MUST TRIP
FOR COMP
AMPS
B1
SETTING
1,2,3,4
80
1,2,4,5,7,8
122
1,3,4,7,8
202
1,3,5
224
1,2,3,6,7
100
1,3,5,6,7,8
210
1,2,4,5,8
126
1,2,3,4
96
1,2,4,5,7,8
146
1,3,4,7,8
242
1,3,5
268
1,2,3,6,7
120
1,3,5,6,7,8
254
1,2,4,5,8
154
1,2,3,4
118
1,2,4,5,7,8
178
1,3,4,7,8
294
1,3,5
326
1,2,3,6,7
146
1,3,5,6,7,8
308
1,2,4,5,8
186
1,2,3,4
142
1,2,4,5,7,8
216
1,3,4,7,8
358
1,3,5
398
1,2,3,6,7
178
1,3,5,6,7,8
374
1,2,4,5,8
226
1,2,3,5
142
1,2,5,6,7,8
216
1,4,5,6,7,8
358
1,4,7
398
1,2,4,5,6
178
1,4,5,8
374
1,2,5,7,8
226
1,2,4,5,6,8
142
1,3,4,5,6,7,8
216
1,6,8
358
2,3,4,6,8
398
1,2,5,6,7,8
178
2,3,4,5,6,7
374
1,3,4,5,7,8
226
1,2,4,5,6,8
174
1,3,4,5,6,7,8
264
1,6,8
436
2,3,4,6,8
484
1,2,5,6,7,8
218
2,3,4,5,6,7
460
1,3,4,5,7,8
278
1,2,4,8
174
1,3,5,6
264
2,3,6,8
436
2,4,8
484
1,3,4,5,6,7,8
218
2,4,5,6,8
460
1,3,6,7,8
278
83
COMP A2
COMP B1
MUST TRIP
MUST TRIP
AMPS
AMPS
SETTING
SETTING
80
122
202
224
100
210
126
80
122
202
224
100
210
126
80
122
202
224
100
210
126
80
122
202
224
100
210
126
96
146
242
268
120
254
154
118
178
294
326
146
308
186
118
178
294
326
146
308
186
142
216
358
398
178
374
226

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents