Carrier 30HXA Installation Instructions Manual

Carrier 30HXA Installation Instructions Manual

Water-cooled and condenserless chillers

Advertisement

CONTENTS

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-27
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . 1
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 1
Step 3 — Piping Connections . . . . . . . . . . . . . . . . . 9
• COOLER FLUID, VENT, AND DRAIN
• BRINE UNITS
• PREPARATION FOR YEAR-ROUND
OPERATION
• 30HXA REFRIGERANT PIPING
• 30HXC CONDENSER CONNECTIONS
• INSTALL PRESSURE RELIEF REFRIGERANT
VENT PIPING
Step 4 — Make Electrical Connections . . . . . . . 14
• FIELD POWER CONNECTIONS
• FIELD CONTROL POWER CONNECTIONS
Step 5 — Install Accessories . . . . . . . . . . . . . . . . 26
• ELECTRICAL
• 30HXA LOW-AMBIENT OPERATION
• MINIMUM LOAD ACCESSORY
• MISCELLANEOUS ACCESSORIES
Step 6 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . . 26
• 30HXC UNITS
• 30HXA UNITS
Step 7 — Refrigerant Charge . . . . . . . . . . . . . . . . 26
• 30HXC UNITS
• 30HXA UNITS
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical compo-
nents, and equipment location. Only trained, qualified
installers and service mechanics should install, start up, and
service this equipment.
When working on the equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
INTRODUCTION
These instructions cover installation of 30HX liquid chill-
ers with electronic controls and units with factory-installed
options (FIOPSs).
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 903
Tab
5c
Water-Cooled and Condenserless Chillers

Installation Instructions

Page
Catalog No. 563-052
Printed in U.S.A.
30HXA,HXC076-186
IMPORTANT: This equipment generates, uses, and can
radiate radio frequency energy. If not installed and
used in accordance with these instructions, this equip-
ment may cause radio interference. The equipment has
been tested and found to comply with the limits of a
Class A computing device as defined by the FCC
(Federal Communications Commission, U.S.A.) Regu-
lations, Subpart J of Part 15, which are designed to
provide reasonable protection against such interfer-
ence when operated in a commercial environment.
INSTALLATION
Step 1 — Inspect Shipment —
age upon arrival. If damage is found, file a claim with the
shipping company right away. Do not store units in an area
exposed to weather because of sensitive control mecha-
nisms and electronic devices.
Locate unit indoors. When considering unit location, con-
sult National Electrical Code (NEC, U.S.A.) and local code
requirements. Allow sufficient space for wiring, piping, and
service. Install unit in an area which will not be exposed to
subfreezing weather. See Fig. 1-4 for clearance details.
Allow the following clearances for service access:
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft (914 mm)
Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ft (610 mm)
Ends . . . . . . . . . . . . . . . tube removal at one (either) end;
Be sure surface beneath the unit is level and is capable of
supporting the operating weight of the unit. See Fig. 5 and
Tables 1A and 1B for unit operating weights. If necessary,
add supporting structure (steel beams or reinforced concrete
slabs) to floor to transfer weight to nearest beams.
Step 2 — Rig and Place Unit
Rig unit from the top heat exchanger only. Rigging from
the bottom heat exchanger will cause the unit to be lifted
unsafely. Personal injury or damage to the unit may
occur.
Do not remove unit from skid until unit is in its
final location. Rig from the rigging holes provided in the top
heat exchanger. See Fig. 1-5 for rigging and center of grav-
ity information. Lower the unit carefully onto the floor or
roller. Push or pull only on the skid, not the unit. If the
unit is moved on rollers, use a minimum of 3 evenly-spaced
rollers.
Form 30HX-1SI
Pg 1
50/60 Hz
Inspect unit for dam-
3 ft (914 mm) at opposite end.
Copy continued on page 9.
5-96
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 30HXA

  • Page 1: Installation Instructions

    • COOLER FLUID, VENT, AND DRAIN • BRINE UNITS • PREPARATION FOR YEAR-ROUND OPERATION • 30HXA REFRIGERANT PIPING • 30HXC CONDENSER CONNECTIONS • INSTALL PRESSURE RELIEF REFRIGERANT VENT PIPING Step 4 — Make Electrical Connections ..14 •...
  • Page 2 UNIT 30HXC 102.12 45.87 45.87 9.87 (2594) (1165) (1165) (251) 102.12 45.87 45.87 9.87 (2594) (1165) (1165) (251) 102.12 37.63 54.12 9.87 (2594) (956) (1375) (251) 102.12 37.63 54.12 10.47 (2594) (956) (1375) (266) 132.56 72.12 50.63 9.87 (3367) (1832) (1286) (251) 132.56...
  • Page 3 DIMENSIONS — in. (mm) UNIT 30HXC 72.12 50.63 2.00 (1832) (1286) (51) 61.37 61.37 2.00 (1559) (1559) (51) 61.37 61.37 2.00 (1559) (1559) (51) Fig. 2 — Base Unit Dimensions, 30HXC161-186 Units NOTES: Denotes center of gravity. 2. Dimensions are in inches. Dimensions ( ) are in millimeters. 3.
  • Page 4 UNIT 30HXA 102.12 45.87 45.87 27.81 9.36 (2594) (1165) (1165) (706) (236) 102.12 45.87 45.87 27.81 9.36 (2594) (1165) (1165) (706) (236) 102.12 37.63 54.12 27.81 9.36 (2594) (956) (1375) (706) (236) 102.12 37.63 54.12 28.41 10.28 (2594) (956) (1375)
  • Page 5 UNIT 30HXA 72.12 50.63 (1832) (1386) 61.37 61.37 (1559) (1559) 61.37 61.37 (1559) (1559) Fig. 4 — Base Unit Dimensions, 30HXA161-186 Units NOTES: Denotes center of gravity. 2. Dimensions are in inches. Dimensions ( ) are in millimeters. 3. Recommended service clearance around unit (front, back, and one side) is 36 (914).
  • Page 6 (770) (532) 1890 1346 (857) (610) 1946 1241 (883) (563) 1996 1265 (905) (574) Fig. 5 — Rigging Information 30HXA UNITS — Lb (Kg) MOUNTING PLATE NO. 1326 (252) (360) (190) (420) (601) 1340 (252) (362) (190) (421) (608) 1350...
  • Page 7 (psig) Maximum Water-Side Pressure (psig) Water Connections (in.) Inlet and Outlet Drain (NPT) *Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. Table 1A — Physical Data, English 5723 5855 6177 6415 4744...
  • Page 8 Maximum Water-Side 2068 Pressure (kPa) Water Connections (in.) Inlet and Outlet Drain (NPT) ⁄ *Charges listed are for 30HXC units. The 30HXA units are shipped with a holding charge only. Table 1B — Physical Data, SI 2596 2656 2802 2910 2933...
  • Page 9 IMPORTANT: Some of the unit skids are larger than standard door openings. Be sure that the path to the unit’s final destination is wide enough to accommo- date unit shipping skid. Remove the skid if necessary. If skid is removed and rollers are used, attach rollers to unit tube sheets while moving unit.
  • Page 11 1. Piping shown is for general point-of-connection only and is not in- tended to show details for a specific installation. Certified field wir- ing and dimensional drawings are available upon request. The 30HXA units should be installed using certified drawings.
  • Page 12 IMPORTANT: There is a Schrader-type fitting in each of the two MUST BE REMOVED before running the line. R-22 The 30HXA units are shipped from the factory with a hold- Psig ing charge of R-134a. Before opening the refrigerant sys- 195.9...
  • Page 13 120 F (48.9 C) saturated condensing temperature, and 105 F (40.6 C) liquid refrigerant temperature. 2. Size each circuit separately. Fig. 10 — R-134a Discharge Line Sizing, 30HXA Units Fig. 11 — Field-Supplied ⁄ -in. Copper Tube, 30HXA Units...
  • Page 14 There are 2 relief valves for the cooler; one on each circuit. The 30HXA high side relief valve is provided with a 5/8 in. SAE (Society of Automotive Engineers, U.S.A.) flare connection. The 30HXC high side relief valves are provided with a 3/4 in.
  • Page 15 Table 4A — Unit Electrical Data, 30HXC Units* VOLTAGE Supplied UNIT Nameplate 30HXC (3 Ph) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50...
  • Page 16 MOCP — Maximum Overcurrent Protection — Rated Load Amps — Wye-Delta Start — Across-the-Line Start *Refer to Carrier’s electronic catalog for the most current electrical data. †Wye-Delta Start is standard. Not available in across-the-line start. **The 30HX186 units have 2 terminal blocks/non-fused disconnects and 6 parallel conductors/non-fused disconnects.
  • Page 17 Table 4B — Unit Electrical Data, 30HXA Units* VOLTAGE Supplied UNIT Nameplate 30HXA (3 Ph) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60...
  • Page 18 Table 4B — Unit Electrical Data, 30HXA Units* (cont) VOLTAGE Supplied UNIT Nameplate 30HXA (3 Ph) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 LEGEND — Maximum Instantaneous Current Flow during start-up...
  • Page 19 Table 5A — Compressor Electrical Data, 30HXC Units NAMEPLATE UNIT SIZE V-Hz 30HXC (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 076-WD 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 086-WD 380-60 230-50...
  • Page 20 Table 5A — Compressor Electrical Data, 30HXC Units (cont) NAMEPLATE UNIT SIZE V-Hz 30HXC (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 126-WD 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 136-WD 380-60...
  • Page 21 Table 5A — Compressor Electrical Data, 30HXC Units (cont) NAMEPLATE UNIT SIZE V-Hz 30HXC (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 186-WD 380-60 230-50 346-50 380/415-50 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps —...
  • Page 22 Table 5B — Compressor Electrical Data, 30HXA Units NAMEPLATE UNIT SIZE V-Hz 30HXA (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 076-WD 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60...
  • Page 23 Table 5B — Compressor Electrical Data, 30HXA Units (cont) NAMEPLATE UNIT SIZE V-Hz 30HXA (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 126-WD 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60...
  • Page 24 Table 5B — Compressor Electrical Data, 30HXA Units (cont) NAMEPLATE UNIT SIZE V-Hz 30HXA (3 Phase) 208/230-60 460-60 575-60 380-60 230-50 346-50 380/415-50 208/230-60 460-60 575-60 186-WD 380-60 230-50 346-50 380/415-50 LEGEND LRA — Locked Rotor Amps RLA — Rated Load Amps —...
  • Page 25 7. Terminals 2 and 3 of TB2 are for alarm. The maximum load allowed for the alarm is 125 va sealed, 1250 va inrush. Fig. 13 — Field Control Wiring LEGEND — Alarm — Carrier Comfort Network COMM — Communications CWFS —...
  • Page 26 30HXA UNITS — These units are shipped with a holding charge of R-134a. Leak test and dehydrate the complete sys- tem (including both field and factory installed piping).
  • Page 27 Carrier Standard Services Techniques Manual as required. 30HXA UNITS — The 30HXA units are shipped with a hold- ing charge of R-134a. The complete charge for the 30HXA, the remote condenser(s), and interconnecting piping must be field supplied.
  • Page 28 For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included. Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 903 Catalog No.

Table of Contents