Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 129

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

The MMV also provides real time monitoring of key inputs
and outputs. The collective group is displayed through
para-meters 50-56 and all values are read only.
• P50 FAULT HISTORY — Last 8 faults
• P51: SOFTWARE version
• P52: DC BUS VOLTAGE — in percent of nominal.
Usually rated input voltage x 1.4.
• P53: MOTOR VOLTAGE — in percent of rated output
voltage
• P54: LOAD — in percent of drives rated output current
rating
• P55: VDC INPUT — in percent of maximum input: 50
will indicate full scale which is 5 v
• P56: 4-20 mA INPUT — in percent of maximum input:
20% = 4 mA, 100% = 20 mA
Fault codes:
The drive is programmed to automatically restart after a fault
and will attempt to restart three times after a fault (the drive
will not restart after CF, cF, GF, F1, F2-F9, or Fo faults). If all
three restart attempts are unsuccessful, the drive will trip into
FAULT CODE
High Temperature Fault: Ambient temperature is too high;
AF
Cooling fan has failed (if equipped).
Control Fault: A blank EPM, or an EPM with
CF
corrupted data has been installed.
Incompatibility Fault: An EPM with an incompatible
cF
parameter version has been installed.
Data Fault: User data and OEM defaults in the
GF
EPM are corrupted.
High DC Bus Voltage Fault: Line voltage is too high;
HF
Deceleration rate is too fast; Overhauling load.
Serial Fault: The watchdog timer has timed out,
JF
indicating that the serial link has been lost.
LF
Low DC Bus Voltage Fault: Line voltage is too low.
Output Transistor Fault: Phase to phase or phase to ground
OF
short circuit on the output; Failed output transistor; Boost
settings are too high; Acceleration rate is too fast.
Current Overload Fault: VFD is undersized for the applica-
PF
tion; Mechanical problem with the driven equipment.
Single-phase Fault: Single-phase input power
SF
has been applied to a three-phase drive.
F1
EPM Fault: The EPM is missing or damaged.
Internal Faults: The control board has sensed a
F2-F9, Fo
problem.
Drive display = '---'
Start contact is not closed.
even though drive
should be running
Drive display = 8.0 Hz
Control signal is at 4 mA
even though fan should
be running faster
Speed signal lost. Drive will operate at 57 (or 47) Hz
VFD flashes 57
until reset or loss of start command. Resetting
(or 47) and LCS
requires cycling start command (or power).
VFD flashes
Start contact is not closed.
"LCS and - - -"
LC
Fault lockout — 3 or more unsuccessful starts
FAULT CODE
CL
CURRENT LIMIT
Er
ERROR
GE
GE
LC
FAULT LOCKOUT
SP
START PENDING
Table 4: Fault Codes
DESCRIPTION
Table 5: Status Indication
FAULT NAME
The output has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive
is reducing the output frequency to reduce the output current. If the drive remains in
CURRENT LIMIT for too long, it can trip into a CURRENT OVERLOAD fault (PF).
Invalid data has been entered.
"GE" will be displayed if an attempt is made to change the OEM default settings
when the drive is operating in the OEM mode (see Parameter 48).
Failed three restart attempts. Requires a manual reset.
This is displayed during the first 15 second interval between restart attempts.
FAULT LOCKOUT (LC), which requires a manual reset. See
Tables 4 and 5.
To disable external control mode (5-8) and enter manual
speed control mode:
Change P05 to '01-key pad'
Push
and
arrow key to set manual speed.
To provide manual start/stop control:
Remove start command jumper and install a switch between
the appropriate start terminals.
Loss of CCN communications:
CCN communications with external control systems can be
affected by high frequency electrical noise generated by
Motormaster V control. Ensure unit is well grounded to elimi-
nate ground currents along communication lines.
If communications are lost only while Motormaster V control is
in operation, order a signal isolator/repeater (CEAS420876-2)
and power supplies (CEAS221045-01, 2 required) for the CCN
communication line.
Check cooling fan operation
Perform a factory reset using Parameter 48 — PROGRAM SELECTION.
See Programming Notes (Step 6).
Either remove the EPM or perform a factory reset
(Parameter 48) to change the parameter version of the
EPM to match the parameter version of the drive.
Restore factory defaults by toggling P48 to another mode.
Then set P48 to desired mode to restore all defaults for that mode.
See configuration section (Step 2). If that does not work, replace EPM.
Check line voltage — set P01 appropriately
Check serial connection (computer)
Check settings for P15
Check settings in communication software to match P15
Check line voltage — set P01 appropriately
Reduce boost or increase acceleration values.
If unsuccessful, replace drive.
Check line voltage — set P01 appropriately
Check for dirty coils
Check for motor bearing failure
Check input power phasing
Consult factory.
Check auxiliary contact for proper operation and configuration. See configu-
ration section (Step 5).
Saturated condensing temperature is below setpoint
in Comfort Link controls.
In stand-alone mode: In external control mode (30GXN,R)
check wiring from unit controls J8 for 4-20 mA signal.
Drive runs at 57 Hz in modes 5,6 and 47 Hz in modes 7,8.
Check auxiliary contact for proper operation and configuration. See configu-
ration section (Step 5).
View PSD: Fault History to determine.
DESCRIPTION
129
SOLUTION