Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 22

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

Table 12  Configuration Mode and Sub-Mode Directory (cont)
SUB-
KEYPAD
ITEM
MODE
ENTRY
OPT1
FLUD
ENTER
MLVS
HPCT
VHPT
PRTS
CPC
CNP.I
CNPC
CWT.S
EMM
OPT2
CTRL
ENTER
CCNA
CCNB
BAUD
LOAD
LLCS
CP.SQ
LCWT
DELY
CLS.C
ICE.M
C.UNB
NO.FL
W.MSG
ALR.C
DISPLAY
EXPANSION
X
COOLER FLUID
YES/NO
MIN LOAD VALVE SELCT
X
HEAD PRESS CONTROL TYPE
X
VAR HEAD PRESSURE SELECT
YES/NO
PRESSURE TRANSDUCERS
ON/OFF
COOLER PUMP CONTROL
ON/OFF
CONDENSER PUMP INTERLOCK
X
CONDENSER PUMP CONTROL
YES/NO
CONDENSER FLUID SENSORS
YES/NO
EMM MODULE INSTALLED
X
CONTROL METHOD
XXX
CCN ADDRESS
XXX
CCN BUS NUMBER
X
CCN BAUD RATE
X
LOADING SEQUENCE SELECT
X
LEAD/LAG SEQUENCE SELECT
X
COMPRESSOR SEQUENCE
XX.X ∆F
HIGH LCW ALERT LIMIT
XX
MINUTES OFF TIME
ENBL/DSBL
CLOSE CONTROL SELECT
ENBL/DSBL
ICE MODE ENABLE
XX %
CURRENT UNBALANCE SETPOINT
ENBL/DSBL
ENABLE NO FLOW DETECTION
ENBL/DSBL
WINTERIZE ALERT CONFIG
X
ALARM RELAY USAGE
ITEM
Default: Water
Water
Medium Temperature Brine
Low Temperature Brine (30HX only)
Minimum Load Valve
No Control
Air Cooled (30GXN,R, 30HXA default)
Water Cooled (30HXC default)
Common Cond (30HXA Common Condenser)
Ind Cond (30HXA Independent Condenser)
None (30HX, 30GX No Motormaster)
4-20 mA (2-10 vdc)(30GX with Motormaster)
0-20 mA (0-10 vdc)
20-0 mA (10-0 vdc)
Default: Yes
Default: Off
Default: Off
(Does not require condenser pump control)
Default: No Control
No Control
On when occupied
On with compressor(s)
Default: No
Default: Switch
Switch = Enable/Off/Remote Contact
7 Day Occ = 7 Day Schedule
Occupancy = CCN Occupancy
CCN = CCN Control
Default: 1
Range: 1 to 239
Default: 0
Range: 0 to 239
Default: 9600
2400
4800
9600
19,200
38,400
Default: Equal
Equal
Staged
Default: Automatic
Automatic
Circuit A Leads
Circuit B Leads
Default: Automatic
Automatic
Compressor 1 Leads
Compressor 2 Leads
Default: 60
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
Default: Disable
Default: Disable
Default: 15%
Range: 10 to 25%
Default: Enable
Default: Enable
Default: Alerts + Alarms
Alerts + Alarms
Alarms Only
Off
22