Table 12  Configuration Mode and Sub-Mode Directory (cont)
SUB
KEYPAD
ITEM
MODE
ENTRY
SLCT
CLSP
ENTER
HTSP
RL.S
CRMP
HRMP
HCSW
Z.GN
BRN.L
SERV
H.PGN
ENTER
H.IGN
H.DGN
H.MIN
MT.SP
BR.FZ
MC.SP
EX.S.A
EX.S.B
EN.A1
EN.A2
EN.B1
EN.B2
W.DNE
ECON
EVPS
LWTC
AP.SP
BCST
TD.B.C
ENTER
OAT.B
GS.BC
BC.AK
DISPLAY
EXPANSION
X
COOLING SETPOINT SELECT
X
HEATING SETPOINT SELECT
ENBL/DSBL
RAMP LOAD SELECT
X.X
COOLING RAMP LOADING
X.X
HEATING RAMP LOADING
COOL/HEAT
HEAT COOL SELECT
X.X
DEADBAND MULTIPLIER
YES/NO
HXC BRINE CONFIG LOCK
XX.X
HEAD PRESSURE P GAIN
XX.X
HEAD PRESSURE I GAIN
XX.X
HEAD PRESSURE D GAIN
XXX.X
WATER VALVE MINIMUM POS.
XXX.X °F
MOTOR TEMP SETPOINT
XXX.X °F
BRINE FREEZE POINT
XXX.X °F
MAX. COND. TEMP SETPOINT
XX.X %
EXVA START POSITION
XX.X %
EXVB START POSITION
ENBL/DSBL
ENABLE COMPRESSOR A1
ENBL/DSBL
ENABLE COMPRESSOR A2
ENBL/DSBL
ENABLE COMPRESSOR B1
ENBL/DSBL
ENABLE COMPRESSOR B2
YES/NO
WINTERIZATION PERFORMED
YES/NO
ECONOMIZED
X
NUMBER OF EVAP. PASSES
A/B
CIRCUIT WITH LWT SENSOR
XXX.X °F
APPROACH SETPOINT
ON/OFF
CCN TIME/DATE BROADCAST
ON/OFF
CCN OAT BROADCAST
ON/OFF
GLOBAL SCHEDULE BROADCAST
ON/OFF
BROADCAST ACKNOWLEDGER
24
ITEM
Default: Single
Single
Dual Switch
Dual 7 day
Dual CCN Occupied
4 to 20 mA Input (requires EMM)
Default: Single
Single
Dual Switch
Dual 7 day
Dual CCN Occupied
4 to 20 mA Input (requires EMM)
Default: Enable
Default: 1.0
Range: 0.2 to 2.0
Default: 1.0
Range: 0.2 to 2.0
Default: Cool
Default: 2.0
Range: 1.0 to 4.0
Default: No
Yes, if brine FIOP is installed (liquid line
solenoid valves).
Default: 1.0
Range: –20 to 20
Default: 0.1
Range: –20 to 20
Default: 0.0
Range: –20 to 20
Default: 20%
Range: 0 to 100%
Default: 200 F (170 F for Brine)
Default: 34 F
Range: –20 to 34 F
Default: 152 F (GXN,R)
Range: 100 F To Default
Default: 20 %
Range: 0 T0 40 %
Default: 20 %
Range: 0 To 40 %
Default: Enable (All)
Disable (HX076-186, GXN,R080-178)
Enable (HX206-271, GXN,R204-350)
Default: Enable (All)
Disable (HX076-271, GXN,R080-268
Enable (GXN,R281-350)
No (30HX076-146, 30GXN,R080-106,114)
Yes (30HX161-271,30GXN,R108,118-350)
Range: 1 To 4
According to number of cooler passes.
Default: 3.0 F
Range: 0.1 to 20.0 F
Default: Off
Default: Off
Default: Off
Default: Off
COMMENT
145 F (HXA)
118 F (HXC)