Building Interface —
The 30GXN,GXR,HX chiller can
be interfaced with multi-vendor control systems through 3 levels
of inter-operability using BacLink, DataPort™, or DataLINK™
devices. BacLink functions as a gateway between a CCN and a
BACnet system to facilitate the passing of data from the CCN to
BACnet. The Carrier DataPort is an interface device that allows
other HVAC control systems to "read only" values in system
elements connected to a CCN communication bus. The Carrier
CCN Table
Description
Name
GENERAL PARAMETERS
Control Mode
Occupied
CCN Chiller
A_UNIT
Alarm State
Active Demand Limit
Override Modes In Effect
Percent Total Capacity
Active Setpoint
Control Point
Entering Fluid Temp
Leaving Fluid Temp
Emergency Stop
Minutes Left for Start
Heat/Cool Select
CIRC. A DISCRETE OUTPUTS
Compressor A1 Relay
Compressor A2 Relay
Loader A1 Relay
Loader A2 Relay
Minimum Load Valve
Oil Heater
Motor Cooling A1 Solenoid
CIRCADIO
Motor Cooling A2 Solenoid
Oil Pump
Oil Solenoid A1
Oil Solenoid A2
CIRC. A DISCRETE INPUTS
Compressor A1 Feedback
Compressor A2 Feedback
Oil Level Switch
CIRCUIT A ANALOG VALUES
Percent Total Capacity
Percent Available Cap.
Circuit Running Current
Discharge Pressure
Suction Pressure
Economizer Pressure
Discharge Superheat Temp
Discharge Gas Temp
Discharge Gas Temp – A1
Discharge Gas Temp – A2
Saturated Condensing Tmp
Saturated Suction Temp
EXV% Open
CIRCA_AN
Variable Head Press Pct.
COMP A1 ANALOG VALUES
A1 Oil Pressure Diff.
A1 Oil Pressure
A1 Motor Temperature
Comp A1 Running Current
Comp A1 % Must Trip Amps
COMP A2 ANALOG VALUES
A2 Oil Pressure Diff.
A2 Oil Pressure
A2 Motor Temperature
Comp A2 Running Current
Comp A2 % Must Trip Amps
APPENDIX D
Object Definitions
30GXN/GXR/HXA/HXC Series 6 with Software Version 1.1 and later
Status
0 = Service Test
1 = OFF Local
2 = OFF CCN
3 = OFF Clock
4 = OFF Emergency
5 = ON Local
6 = ON CCN
7 = ON Clock
No/Yes
Start/Stop
Normal/Alert/Alarm
0 to 100
No/Yes
0 to 100
-20 to 70 (-28.8 to 21.1)
-20 to 70 (-28.8 to 21.1)
snnn.n
snnn.n
Enable/Emstop
00:00 to 15:00
Heat/Cool
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Close/Open
0 to 100
0 to 100
0 to 1200
nnn.n
nnn.n
nnn.n
snnn.n
nnn.n
nnn.n
nnn.n
snnn.n
snnn.n
0 to 100
0 to 100
nnn.n
nnn.n
nnn.n
0 to 600
0 to 100
nnn.n
nnn.n
nnn.n
0 to 600
0 to 100
DataLINK device is an interface device that allows other HVAC
control systems to read and change ("read/write") values in
system elements connected to a CCN bus. Both DataPort and
DataLINK devices request data from a specified CCN system
element and translate this data into ASCII characters off
network. Information from the 30GXN,GXR,HX chiller control
to support interface are listed in the following tables.
Units
Point
STAT
OCC
CHIL_S_S
ALM
DEM_LIM
%
MODE
CAP_T
%
SP
°F (°C)
CTRL_PNT
°F (°C)
EWT
°F (°C)
LWT
°F (°C)
EMSTOP
MIN_LEFT
Minutes
HEATCOOL
K_A1_RLY
K_A2_RLY
LOADR_A1
LOADR_A2
MLV
OILA_HTR
MTRCL_A1
MTRCL_A2
OILPMP_A
OILSL_A1
OILSL_A2
K_A1_FBK
K_A2_FBK
OILA_SW
CAPA_T
%
CAPA_A
%
A_CURR
Amps
PSIG (KPA)
DP_A
PSIG (KPA)
SP_A
PSIG (KPA)
ECNP_A
°F (°C)
SH_A
°F (°C)
DISTMP_A
°F (°C)
DISTMPA1
°F (°C)
DISTMPA2
°F (°C)
TMP_SCTA
°F (°C)
TMP_SSTA
%
EXV_A
%
VHPA
DOP_A1
PSIG (KPA)
OP_A1
PSIG (KPA)
°F (°C)
TMTR_A1
Amps
A1_CURR
%
A1_MTA
PSIG (KPA)
DOP_A2
PSIG (KPA)
OP_A2
°F (°C)
TMTR_A2
Amps
A2_CURR
%
A2_MTA
92
DataPort
DataLink
BAClink
RO
RO
RO
RO
RO
RO
RO
RW
RW
RO
RO
RO
RO
RW
RW
RO
RO
NA
RO
RO
RO
RO
RO
NA
RO
RW
RW
RO
RO
RO
RO
RO
RO
RO
RW
RW
RO
RO
NA
RO
RW
RW
RO
RO
RO
RO
RO
RO
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
RO
RO
RO
RO
RO
RO
NA
RO
RO
RO
RO
RO
RO
RO
RO
NA
RO
RO
RO
RO
RO
NA
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA
RO
RO
NA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents