Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 45

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

ALARM/
ALARM OR
ALERT CODE
ALERT
T071
Alert
Cir. B Discharge Gas
Thermistor Failure
T073
Alert
Outside Air Tempera-
ture Thermistor
Failure
T074
Alert
Space Temperature
Thermistor Failure
T075
Alert
Compressor A1
Discharge Gas
Thermistor Failure
T076
Alert
Compressor A2
Discharge Gas
Thermistor Failure
T077
Alert
Compressor B1
Discharge Gas
Thermistor Failure
T078
Alert
Compressor B2
Discharge Gas
Thermistor Failure
T079
Alert
Lead/Lag Leaving
Fluid Temperature
Thermistor Failure
T090
Alert
Circuit A Discharge
Pressure Transducer
Failure
T091
Alert
Circuit B Discharge
Pressure Transducer
Failure
T092
Alert
Circuit A Suction
Pressure Transducer
Failure
T093
Alert
Circuit B Suction
Pressure Transducer
Failure
T094
Alert
Comp A1 Oil Pres-
sure Transducer
Failure
T095
Alert
Comp A2 Oil Pres-
sure Transducer
Failure
T096
Alert
Comp B1 Oil Pres-
sure Transducer
Failure
T097
Alert
Comp B2 Oil Pres-
sure Transducer
Failure
T098
Alert
Circuit A Economizer
Pressure Transducer
Failure – 1
Alert
Circuit A Economizer
Pressure Transducer
Failure – 2
T099
Alert
Circuit B Economizer
Pressure Transducer
Failure – 1
Alert
Circuit B Economizer
Pressure Transducer
Failure – 2
T110
Alert
Circuit A Loss of
Charge
T111
Alert
Circuit B Loss of
Charge
Table 32  Alarm and Alert Codes (cont)
WHY WAS THIS ALARM
DESCRIPTION
GENERATED?
Average of compressor B1
and B2 (if installed)
sensors > 210° F for
30 seconds.
Thermistor outside range of
–40 to 240 F (–40 to 116 C)
Thermistor outside range of
–40 to 240 F (–40 to 116 C)
Thermistor outside range of –
40 to 240° F (–40 to 116° C)
Thermistor outside range of –
40 to 240° F (–40 to 116° C)
Thermistor outside range of –
40 to 240° F (–40 to 116° C)
Thermistor outside range of –
40 to 240° F (–40 to 116° C)
Thermistor outside range of
–40 to 240 F (–40 to 116 C)
Voltage ratio more than
98.9% or less than 6%.
Voltage ratio more than
98.9% or less than 6%.
Voltage ratio more than
99.9% or less than 0.5% for
50 seconds.
Voltage ratio more than
99.9% or less than 0.5% for
50 seconds.
Voltage ratio more than
98.9% or less than 6%.
Voltage ratio more than
98.9% or less than 6%.
Voltage ratio more than
98.9% or less than 6%.
Voltage ratio more than
98.9% or less than 6%.
Voltage ratio more than
99.9% or less than 0.5% for
50 seconds.
Economizer pressure is more
than 12 psi (83 kPa) less than
suction pressure.
Voltage ratio more than
99.9% or less than 0.5% for
50 seconds.
Economizer pressure is more
than 12 psi (83 kPa) less than
suction pressure.
Discharge pressure reading
< 10 psig for 30 seconds.
Discharge pressure reading
< 10 psig for 30 seconds.
ACTION TAKEN BY
CONTROL
Circuit B shut down
Reset disabled. Runs
under normal control/
set points.
Reset disabled. Runs
under normal control/
set points.
Comp A1 shut down
Comp A2 shut down
Comp B1 shut down
Comp B2 shut down
Breaks Dual Chiller
link if set up for Paral-
lel operation.
Circuit A shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Comp A1 shut down
Comp A2 shut down
Comp B1 shut down
Comp B2 shut down
Circuit A shut down
Circuit A shut down
Circuit B shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
45
RESET
PROBABLE CAUSE
METHOD
Manual
Thermistor failure, damaged
cable/wire, wiring error or
motor cooling solenoid failure.
Automatic Thermistor failure, damaged
cable/wire, wiring error or sen-
sor not installed.
Automatic Thermistor failure, damaged
cable/wire, wiring error or sen-
sor not installed.
Automatic Thermistor failure, damaged
cable/wire, wiring error or
motor cooling solenoid failure.
Automatic Thermistor failure, damaged
cable/wire, wiring error or
motor cooling solenoid failure.
Automatic Thermistor failure, damaged
cable/wire, wiring error or
motor cooling solenoid failure.
Automatic Thermistor failure, damaged
cable/wire, wiring error or
motor cooling solenoid failure.
Automatic Thermistor failure, damaged
cable/wire, wiring error or sen-
sor not installed.
Automatic Transducer failure, poor con-
nection to MBB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to MBB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to MBB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to MBB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to SCB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to SCB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to SCB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to SCB, or wiring
damage/error.
Automatic Transducer failure, poor con-
nection to SCB, or wiring
damage/error.
Manual
Suction and Economizer pres-
sure connectors/wiring are
swapped.
Automatic Transducer failure, poor con-
nection to SCB, or wiring
damage/error.
Manual
Suction and Economizer pres-
sure connectors/wiring are
swapped.
Manual
Refrigerant leak or transducer
failure.
Manual
Refrigerant leak or transducer
failure.