Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 88

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

Each compressor has 2 loaders and the chiller is configured for equal circuit
loading. See Note 2.
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 4-COMPRESSOR UNIT)
COMP
LOADER
STAGE
A1
A1
0
0
1
1
2
1
3
1
4
1
5
1
6
1
7
1
8
1
9
1
10
1
CLOSE CONTROL LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 4-COMPRESSOR UNIT)
COMP
LOADER
STAGE
A1
A1
0
0
1
1
2
1
3
1
3A
1
4
1
5
1
6
1
7
1
7A
1
8
1
9
1
10
1
11
1
LEGEND
0 — Off
1 — On
NOTES:
1. Stages 3A and 7A are not used by the algorithm when increasing stages.
Stages 3 and 7 are not used by the algorithm when decreasing stages.
2. The loading sequence for 30GXN,R281-325 units is the same as those
shown for the 30GXN,R350 above.
APPENDIX B (cont)
The following tables show the loading sequence for a 30GXN,R350 chiller.
LOADER
COMP
A2
A2
0
0
0
0
0
0
1
0
0
1
1
0
1
0
0
1
1
0
1
1
0
1
0
1
1
0
1
1
1
1
1
1
1
LOADER
COMP
A2
A2
0
0
0
0
0
0
1
0
0
1
1
0
0
0
0
0
0
0
1
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
0
1
1
1
1
1
1
1
COMP
LOADER
LOADER
B1
B1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
COMP
LOADER
LOADER
B1
B1
0
0
0
0
0
0
0
0
1
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
88
% TOTAL
COMP
CAPACITY
B2
B2
(50/50 Split)
0
0
0
0
10.0
0
0
18.0
0
0
25.0
0
0
35.0
0
0
43.0
1
0
50.0
1
0
60.0
0
1
70.0
0
1
85.0
1
1
100.0
% TOTAL
COMP
CAPACITY
B2
B2
(50/50 Split)
0
0
0
0
10.0
0
0
18.0
0
0
25.0
0
0
20.0
0
0
28.0
0
0
35.0
0
0
43.0
1
0
50.0
1
0
45.0
1
0
60.0
0
1
70.0
0
1
85.0
1
1
100.0
0.0