Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 40

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

KEYPAD
MODE
ENTRY
CONFIGURATION
ENTER
NOTE: Heating reset values skipped in this example.
Table 30 — Menu Configuration of 4 to 20 mA Cooling Set Point Control
MODE
KEYPAD
(RED LED)
ENTRY
CONFIGURATION
ENTER
Table 29 — Configuring Demand Limit
KEYPAD
SUB-MODE
ITEM
ENTRY
DISP
TEST
ENTER
UNIT
ENTER
TYPE
OPT1
FLUD
ENTER
OPT2
CTRL
ENTER
RSET
CRST
ENTER
CRT1
CRT2
DGRC
DMDC
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
KEYPAD
SUB-MODE
ITEM
ENTRY
DISP
UNIT
OPT1
OPT2
RSET
SLCT
CLSP
ENTER
ENTER
ENTER
ENTER
DISPLAY
ITEM EXPANSION
ON/OFF
Test Display LEDs
X
Unit Type
X
Cooler Fluid
X
Control Method
X
Cooling Reset Type
XXX.X °F
No Cool Reset Temperature
XXX.X °F
Full Cool Reset Temperature
XX.X ∆F
Degrees Cool Reset
X
Demand Limit Select
XXX%
Demand Limit at 20 mA
Loadshed Group
XXX
Number
Loadshed Demand
XXX%
Delta
Maximum Loadshed
XXX MIN
Time
Demand Limit
XXX %
Switch 1
Demand Limit
XXX%
Switch 2
ITEM
DISPLAY
EXPANSION
0
COOLING SETPOINT SELECT
0
0
4
4
40
COMMENT
Default: 0
0 = None
1 = Switch
2 = 4 to 20 mA Input
3 = CCN Loadshed
Default: 100%
Range: 0 to 100
Default: 0
Range: 0 to 99
Default: 0%
Range: 0 to 60%
Default: 60 min.
Range: 0 to 120 min.
Default: 80%
Range: 0 to 100%
Default: 50%
Range: 0 to 100%
COMMENT
Scrolling Stops
Flashing '0'
Select '4'
Change Accepted