Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting page 28

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

KEYPAD
SUB-MODE
ENTRY
GEN.I
ENTER
CRCT
ENTER
4-20
ENTER
Table 17 — Inputs Mode and Sub-Mode Directory
ITEM
DISPLAY
STST
STRT/STOP
FLOW
ON/OFF
CND.F
ON/OFF
DLS1
ON/OFF
DLS2
ON/OFF
ICED
ON/OFF
DUAL
ON/OFF
FKA1
ON/OFF
FKA2
ON/OFF
OIL.A
OPEN/CLSE
A1.CR
XXX AMPS
A2.CR
XXX AMPS
FKB1
ON/OFF
FKB2
ON/OFF
OIL.B
OPEN/CLSE
B1.CR
XXX AMPS
B2.CR
XXX AMPS
DMND
XX.X MA
RSET
XX.X MA
CSP
XX.X MA
HSP
XX.X MA
ITEM
EXPANSION
START/STOP SWITCH
COOLER FLOW SWITCH
CONDENSER FLOW SWITCH
DEMAND LIMIT SWITCH 1
DEMAND LIMIT SWITCH 2
ICE DONE
DUAL SETPOINT SWITCH
COMPRESSOR A1 FEEDBACK
COMPRESSOR A2 FEEDBACK
OIL LEVEL SWITCH
COMP A1 RUNNING CURRENT
COMP A2 RUNNING CURRENT
COMPRESSOR B1 FEEDBACK
COMPRESSOR B2 FEEDBACK
OIL LEVEL SWITCH
COMP B1 RUNNING CURRENT
COMP B2 RUNNING CURRENT
4-20 MA DEMAND SIGNAL
4-20 MA RESET SIGNAL
4-20 MA COOLING SETPOINT
4-20 MA HEATING SETPOINT
28
COMMENT