Safety devices
Photocells
Confi gure contact CX or CY (NC), safety input for photocells.
See CX input functions (Function F 2) or CY (Function F 3) in:
- C1 reopening during closing. When the door is closing, opening the contact causes the door to invert its move-
ment until it is completely open.
- C2 close back up during opening. When the door is opening, opening the contact causes the door to invert its
movement until it is completely closed.
- C3 partial stop. Stop door, if it is moving, with consequent automatic closing (if the automatic closing function
is on);
- C4 obstruction wait. Stop door, if it is moving, which resumes movement once the obstruction is removed.
If unused, contacts CX and CY should be deactivated during programming.