RESIDENCE
4
COMMISSIONING
4.1

Preliminary checks

First ignition is carried out by competent personnel from an authorised
Technical Assistance Service Riello.
Before starting up the boiler, check:
- that the data of the supply networks (electricity, water, gas) correspond
to the label data
- that the extraction pipes of the flue gases and the air suction pipes are
working correctly
- that conditions for regular maintenance are guaranteed if the boiler is
placed inside or between items of furniture
- the seal of the fuel adduction system
- that the fuel flow rate corresponds to values required by the boiler
- that the fuel supply system is sized to provide the correct flow rate to
the boiler, and that it has all the safety and control devices required by
current regulations
- that the circulator rotates freely because, especially after long periods
of inactivity, deposits and/or debris can prevent free rotation. See the
paragraph "3.12 Manual reset of the circulator".
4.2
Programming the boiler
- Position the system's master switch to the "on" position.
If necessary, the interface automatically goes to the clock menu. On the
main screen the icons
,
00:00 is displayed with the first two digits blinking with a frequency of 0.5
sec ON, 0.5 sec OFF.
To set the time and day follow the following instructions:
ƒ set the hour with the
and
ƒ set the minutes with the
ƒ set the day of the week with the
line with the day selected blinks, press the menu MENU key at the icon
Enter
to confirm the time and day setting. The clock blinks for 4sec and
then returns to the main screen
ƒ to exit the time programming without saving the modified values just
press
.
NOTE: It is possible to change the TIME and DAY settings also later by
accessing the TIME parameter in the SETTING menu, or by pressing the
A+C keys for at least 2sec.
A
+
Each time that the boiler is powered a vent cycle is carried out lasting 4 min.
The display shows the message <<VENT AIR PURGING CYCLE IN
PROGRESS>> lighting up the icon RESET.
16
,
and
and ENTER come on while
arrows, then confirm with A
arrows, then confirm with A
and
and
arrows. The segment in
+
C
RESET
MENU
To interrupt the vent cycle press RESET.
Set the boiler to OFF by pressing
Using the interface it is possible to access, using the SETTINGS menu, a
series of parameters that can be programmed to allow you to personalise
the operation of the boiler based on the type of system.
Set the parameters according to the desired operating modes.
4.3
Time band scheduling function (room thermostat)
If the heating system is managed by a room thermostat, and therefore
without programming timing, the programming timing on the boiler interface
can be enabled by setting in the CH menu the parameter POR = 1.
To access the programming timing menu press the keys B+D for at least
2sec.
+
B
The displays appears as in the following figure:
Using the
,
arrows select the day or the pre-selected group of days:
1-2-3-4-5-6-7 programming the individual days
1-5 programming from Monday to Friday
6-7 programming from Saturday to Sunday
1-7 programming the entire week
With the
key you confirm the selection made and you pass to
the programming of the time bands, with the
programming timing confirming the changes made.
With the
key you exit without saving the selections.
Setting the Time Bands
- The display shows TIME ON, press
change the time, confirm with
- The display shows TIME OFF, press
,
change the time, confirm with
.
+
D
RESET
MENU
Enter
key you exit the
to set the ignition time, with
.
to set the switching off time, with
.
,