Riello RESIDENCE KIS Series Installer And User Manual page 38

Hide thumbs Also See for RESIDENCE KIS Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 4
RESIDENCE
For fault E041
If the pressure drops below the safety threshold of 0.3 bar the boiler displays
the fault code <<E041 water transducer load the system>> for a transitional
time of 30sec.
When the transitional time has finished, if the fault persists the fault code E040
is displayed.
When the boiler has fault E040 manual loading should be carried out using the
filler tap (
A
) until the pressure is between 1 and 1.5 bar.
Then press RESET.
Boiler faults list
ERROR
CODE
E010
E011
E020
E030
E040
E041
E042
E060
E070
E077
E080
E090
E091
E099
--
--
--
--
List of combustion faults
ERROR
FAULT
CODE
E021
ion alarm
E022
ion alarm
E023
ion alarm
E024
ion alarm
E067
ion alarm
E088
ion alarm
E097
ion alarm
E085
incomplete combustion
E094
incomplete combustion
E095
incomplete combustion
E058
mains voltage fault
E065
current modulation alarm
E086
flue gases obstruction alarm
38
DAY
flame lockout/ACF electronic fault
extraneous flame
limit thermostat
water transducer – load system
water transducer – load system
water pressure transducer fault
domestic hot water probe fault
flow sensor fault
flow sensor overtemperature
flow/return sensor differential alarm
main zone water thermostat
return line probe fault
return line probe overtemperature
outlet/return line probe differential alarm
flue gas probe fault
flue gas probe overtemperature
clean primary heat exchanger
reset attempts exhausted, boiler blocked
water pressure low check system
water pressure high check system
boiler board communication lost
BUS 485 communication lost
These are temporary alarms that if they occur 6 times in an hour they become definitive; the E097 alarm is dis-
played and is followed by post-purging for 45 seconds at the fan's maximum speed.
It is not possible to release the alarm before the end of the post-purging unless the boiler's power supply is
These are temporary alarms that if they occur several times in an hour they become definitive; the last error to
occur is displayed and is followed by a post-purging of 5 minutes at the fan's maximum speed. It is not possible to
release the alarm before the end of the post-purging unless the boiler's power supply is switched off.
Close the filling tap, making sure to hear the mechanical snap.
b
If the drop in pressure is very frequent, contact the Technical Assistance
Centre.
For fault E060
The boiler is working normally, but does not provide any stability of the
domestic hot water temperature that, in any event, is supplied at a tempera-
ture of around 50°C. The intervention of the Technical Assistance Service
is required.
For fault E091
The boiler has an auto-diagnostic system which, based on the total number
of hours in certain operating conditions, can signal the need to clean the
primary exchanger.
The intervention of the Technical Assistance Service is required.
FAULT
fan fault
DESCRIPTION OF ALARM TYPE
switched off.
These are temporary faults that restrict the ignition cycle.
Temporary fault signalled during pre-purging.
Post-purging is maintained for 5 min at maximum fan speed.
A
DESCRIPTION OF
ALARM TYPE
definitive
transitional
definitive
definitive
definitive
transitional
definitive
transitional
transitional
definitive
definitive
transitional
transitional
definitive
definitive
transitional
definitive
transitional
definitive,
not resettable
transitional
transitional
transitional
transitional