Key 2 can stay active if there is a fault to allow the alarm to be reset.
4.25 Interface Stand by
Usually, when there are no faults or heat requests, the display always
shows the temperature measured by the flow sensor.
If within 10 seconds there is no heat request without any key being pressed
the interface goes into stand by.
The display shows the current time, the two points separating the time from
the minutes blink with a frequency of 0.5sec ON and 0.5sec OFF, while the
status icons will be active if necessary:
4.26 Replacing SC08 interface
The system configuration operations need to be carried out by professionally
qualified personnel of the Technical Assistance Centre.
When replacing the SC08 interface board, it might happen that when power
up the user is requested to reset the time and the day of the week (see
paragraph "4.6 First commissioning"). Remember that no programming of
the configuration parameters is needed, the values are recovered from the
control and adjustment board in the boiler.
4.27 Replacing the AKM board
When replacing the AKM adjustment and control board it might be necessary
to re-programme the configuration parameters.
In this case see the SETTINGS MENU to find the board default values, i the
factory settings and personalised settings.
The parameters to be checked and reset if necessary in the event of a
board replacement are:
GAS TYPE
BOILER TYPE
HYDRAULIC CONFIGURATION
WATER TRANSDUCER
AUTO WATER FILL ENABLE
SLIDING OUTLET TANK FLOW TEMP
4.28 Combustion Control Parameters
Even if the parameters regarding the new ACC active combustion control
system are pre-set in the factory, it might be necessary to re-programme
them if the electronic board is replaced.
ƒ Access the technical parameters as explained in the paragraph "3.21
Access to the parameters" entering the INSTALLER password.
ƒ Select COMB with the keys
ƒ Select GAS TYPE.
ƒ Set this parameter based on the type of gas the boiler is using. The
values for this parameter are METHANE = 0 - LPG = 1
ƒ Set the SERVICE password.
ƒ Select the COMB menu and the parameter BOILER TYPE
ƒ Set this parameter based on the type of boiler as shown in the table
25 KIS
30 KIS
35 KIS
40 KIS
ƒ Select COMBUSTION OFFSET.
select this option when replacing the detection
Value 1 = ZERO RESET:
electrode on the burner
Value 2 =
select this option when replacing the AKM electronic
RESTORE:
board
b
If after maintenance work on the elements of the combustion unit
(Repositioning the detection electrode or else replacing/cleaning the
primary heat exchanger, condensate siphon, fan, burner, flue gases
conveyor, gas valve, gas valve diaphragm), the boiler generates one
or more alarms regarding combustion faults, we recommend setting
the main system switch to off for at least 5 minutes.
ENGLISH
and
confirming the selection
BOILER TYPE
1
2
3
4
.
29