Description

2.5 Communication

Wiring
The digital output is passive and implemented exclusively as a switch.
Implementation of the pulse function corresponds to the IEC 62053-31 standard.
(1)
(2)
Figure 2-3
● Pulse length:
Time for which the signal at the digital output is "high". The minimum pulse length is
30 ms and the maximum 500 ms.
● Turn-off time:
Time for which the signal at the digital output is "low". The turn-off time depends on the
measured energy, for example, and can be days or months.
● Minimum turn-off time:
The minimum turn-off time corresponds to the programmed pulse length. 30 ms is the
absolute minimum.
2.5
Communication
Depending on the device version, the devices may be fitted with the following
communications interfaces:
● Ethernet
● RS 485
● M-BUS
The selection of the measured variables available for selection can vary according to the
communication mode selected.
26
Pulse length
Turn-off time
Pulse length and turn-off time
Equipment Manual, 12/2019, L1V30415167B-03