Single-Phase Connection (1P2W) - Siemens SENTRON 7KM PAC2200 Product Manual

Power monitoring device
Hide thumbs Also See for SENTRON 7KM PAC2200:
Table of Contents

Advertisement

2.5.3.2

Single-phase connection (1P2W)

The measurement data is presented on one page.
All measurement data that can be read out via the M-BUS are listed in the following table.
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
Measured variable
Total active energy import tariff 1
Total active energy import tariff 2
Total active energy export tariff 1
Total active energy export tariff 2
Active power L1
Voltage L1-N
Current L1
Total reactive energy import tariff 1
Total reactive energy import tariff 2
Total reactive energy export tariff 1
Total reactive energy export tariff 2
Reactive power L1 (VAR1)
Power factor L1
Frequency
Tariff
Total apparent energy tariff 1
Total apparent energy tariff 2
Apparent power L1
Date/time
Description
2.5 Communication
Length
Format
(bits)
48
INT48
48
INT48
48
INT48
48
INT48
32
FLOAT32
32
FLOAT32
32
FLOAT32
48
INT48
48
INT48
48
INT48
48
INT48
32
FLOAT32
32
FLOAT32
32
FLOAT32
8
INT8
48
INT48
48
INT48
32
FLOAT32
32
time
Unit
Wh
Wh
Wh
Wh
W
V
A
kvarh
kvarh
kvarh
kvarh
kvar
Hz
kVAh
kVAh
kVA
35