Appendix
A.1 Modbus TCP
A.1.11

Modbus command parameters

Addressing the command parameters
You can apply the Modbus function code 0x06 to the command parameters.
Table A- 13
Command parameters
Offset
Number
Name
of r
egisters
60004
1
Reset energy counter
60005
1
Synchronization of the
demand period
60006
1
Switching tariff
60007
1
Acknowledge the diagnos-
tics bits
unsigned long beginning
offset 205)
60008
1
Switching outputs (if pa-
rameterized)
60009
1
Switching command for
vector group
65300
1
Activation of IP / Ethernet
configuration
3) The Modbus Master must acknowledge these diagnostics bits.
116
Unit
-
Min.
-
-
(cf. stored bits in
3)
-
-
-
Format
Value range
unsigned
0 =
all
short
1 =
Active energy import tariff 1
2 =
Active energy import tariff 2
3 =
Active energy export tariff 1
4 =
Active energy export tariff 2
5 =
Reactive energy import
tariff 1
6 =
Reactive energy import
tariff 2
7 =
Reactive energy export
tariff 1
8 =
Reactive energy export
tariff 2
9 =
Apparent energy tariff 1
10 =
Apparent energy tariff 2
unsigned
1 ... 60
short
unsigned
0 =
short
1 =
unsigned
0 ... ffffh
short
unsigned
0ffh ... 1ffh
short
Byte 0
= 0
Byte 1
= 0
Byte 1
= 1
unsigned
High 0 ... 99, Low 0 ... 1
short
High byte group assignment
Low byte 1 = ON, 0 = OFF
unsigned
0
short
Equipment Manual, 12/2019, L1V30415167B-03
Main tariff
Secondary tariff
Digital output 0.0
OFF
ON
Access
W
W
W
W
W
W
W
PAC2200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents