2.2

Measuring inputs

Current measurement
NOTICE
AC current measurement only
The device is not suitable for measuring DC current.
The 5 A device is designed for:
● Measuring current of 5 A for connecting standard current transformers. Each current
measuring input can take a continuous load of 10 A. A momentary overcurrent of up to
100 A and a duration of 1 s is possible.
The current direction can be changed for each phase individually. It is not necessary to
change the terminal connections of the current transformers in the event of connection
errors.
The 65 A device is designed for:
● Direct connection to the low-voltage network.
Voltage measurement
NOTICE
AC voltage measurement only
The device is not suitable for measuring DC voltage.
PAC2200 is designed for:
● Direct measurement on the network.
● Measurement voltage up to 277 V / 480 V. The device is designed for measuring input
voltages up to 277 V to the neutral conductor and for measuring input voltages up to
480 V to the external conductor.