Modbus-Measured Variables With Function Code "0X14 - Siemens SENTRON 7KM PAC2200 Product Manual

Power monitoring device
Hide thumbs Also See for SENTRON 7KM PAC2200:
Table of Contents

Advertisement

Appendix
A.1 Modbus TCP
A.1.4

Modbus-measured variables with function code "0x14"

Addressing the measured variables
The measured variables listed below can be read out via Modbus function code 0x14 "Read
File Record" in two steps.
Step 1 (File Number 1), preset to 10 s
Step 2 (File Number 2), preset to 15 min
Note
Error in the case of inconsistent access to measured values
Please ensure the start offset of the register is correct when making read accesses.
Please ensure the start offset and the number of registers are correct when making write
accesses.
Example: If a value consists of two registers, a read command applied in the second register
will generate an error code. The PAC2200 will also output an error code if a write operation
ends in the middle of a multi-register value.
Abbr. in the "Access"
column
R
W
RW
File
Offset
Address
(FC0x14)
address
FC0x03
FC0x04
1
1
30001
1
3
30003
1
5
30005
1
7
30007
1
9
30009
1
11
30011
1
13
30013
1
15
30015
1
17
30017
1
19
30019
1
21
30021
102
Abbreviations
Read access
Write access
Read and write access
Number
Name
of
registers
2
Time stamp
2
Flags
2
Voltage L1 - N
2
Voltage L2 - N
2
Voltage L3 - N
2
Voltage L1 - L2
2
Voltage L2 - L3
2
Voltage L3 - L1
2
Current L1
2
Current L2
2
Current L3
Format
Unit
Value range
unix_ts
-
uint32_t
-
0= UNFLAGGED
1= FLAGGED
2= SAG
4= SWELL
8= POWER FAIL
Float
V
Float
V
Float
V
Float
V
Float
V
Float
V
Float
A
Float
A
Float
A
Equipment Manual, 12/2019, L1V30415167B-03
Access
R
R
R
R
R
R
R
R
R
R
R
PAC2200