Siemens SENTRON 7KM PAC2200 Product Manual page 87

Power monitoring device
Hide thumbs Also See for SENTRON 7KM PAC2200:
Table of Contents

Advertisement

Power supply (5 A and 65 A devices)
Power supply
Design of the power supply
Work area
Power consumption
Overvoltage category
Measuring accuracy
Applied standards:
● IEC 61557-12
● IEC 62053-21
● IEC 62053-22
● IEC 62053-23
● EN 50470-3:
Measured variable
Voltage
Current
Apparent power
Active power
Reactive power
Total apparent power over all phases
Total active power over all phases
Total reactive power VAR1 over all phases
Cumulated active power
Cumulated reactive power
Total power factor
Line frequency
Active energy
Reactive energy
Active energy according to IEC62053-21
Reactive energy according to IEC62053-23
Measurement accuracy according to EN50470-3
Note:
For the PAC2200 (5A) device, the accuracy of the measurement depends on the quality of
the current transformers used.
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
Technical specifications
8.1 Technical specifications
Wide range AC power supply
100 V - 230 V +/- 20%
5 VA
OVT III
Accuracy class acc. to IEC 61557-12 (K55)
Class 0.5
Class 0.5
Class 1
Class 1
Class 1
Class 1
Class 1
Class 2
Class 1
Class 2
Class 0.5
Class 0.05
Class 1
Class 2
Class 1
Class 2
Class B
85