Establishing connection to the device
To establish a connection to the PAC2200, proceed as follows:
1. Connect the PAC2200 device to the PC or network.
2. When you have connected the device via Ethernet, make sure that the PAC2200 and the
configuration computer are in the same subnet.
3. Open the powerconfig configuration software.
4. On the toolbar, click on the "Search for accessible devices" key or alternatively press the
"F11" key. The "Search for accessible devices" window is displayed.
5. In the "Search for accessible devices" window, click on the "Ethernet" tab if you want to
access the device via Ethernet or "Serial" if
you want to access the device via the RS485 interface:
The "Ethernet" view appears.
– Select the Ethernet interface from the selection list.
– Click on the "Start search" button.
– Select the desired device.
– If necessary, adapt the communication settings.
– To do this, switch the edit mode to "Unlocked". Carry out the required settings in the
The "Serial" view appears.
– Select PAC2200 in the "Search for device" option.
– Enter the communication settings (COM, Port; Address; Baud rate; Format and
– Click on the "Start Search" button.
6. All devices found are shown in the "Result" window.
7. Select the desired device and click on the "Create devices" button.
The selected device is added.
8. In menu item "Views", select the sub-menu "Parameters".
The "Parameter" window is displayed.
9. In the "Properties" window, click on the "Load to PC" button.
The configuration is loaded from the device to the PC.
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
menu options "IP address", "Network mask", "Gateway" etc. Click on the button "Load
changes to configuration parameters into device(s)".
Protocol).
Commissioning
6.3 Parameterizing the device
65