Operation
5.3 Supporting software
Note
You launch the Online Help in powerconfig by pressing the *F1* key.
5.3.3

Web server

The device can be read out with a PC/notebook via a website using the web server
integrated in the device. Communication is performed via the Modbus TCP protocol.
The web server provides the following functions:
● Device information such as serial number, firmware status etc.
● View and evaluation of the measured values
Start web server:
1. Connect the device to the PC or network via the Ethernet interface.
2. Make sure that the PAC2200 and the configuration computer are in the same subnet.
3. Enter the IP address of the device in the browser.
HTTP-Port: 80 (default setting)
Note
The web server can be deactivated with the HTTP Port: 0 setting.
58
Equipment Manual, 12/2019, L1V30415167B-03